S5C10 Residential care building: Concession
Specification 5 Fire-resisting construction · NCC 2019: Spec C1.1: 2.9
(1) In a Class 3 building protected with a sprinkler system complying with Specification 17 and used as a residential care building, any FRL criterion prescribed in Tables S5C11a, S5C11d, S5C11e, S5C11f, S5C11g, S5C21a, S5C21d, S5C21e, S5C21f, S5C21g, S5C24a, S5C24c or S5C24d —
for any floor and any load bearing wall, may be reduced to 60, except any FRL criterion of 90 for an external wall must be maintained when tested from the outside; and
for any non-load bearing internal wall, need not apply if—
it is lined on each side with standard grade plasterboard not less than 13 mm thick or similar non-combustible material; and
it extends—
to the underside of the floor next above; or
to the underside of a ceiling lined with standard grade plasterboard not less than 13 mm thick or a material with at least an equivalent level of fire protection; or
to the underside of a non-combustible roof covering; and
any insulation installed in the cavity of the wall is non-combustible; and
any construction joint, space or the like between the top of the wall and the floor, ceiling or roof is smoke sealed with intumescent putty or other suitable material.
(2) The concession described at (1) does not apply to fire-protected timber building elements.