Specification clause · NCC 2025 Volume One

S5C9 Carparks and ancillary uses for Class 2 and 3 buildings

Specification 5 Fire-resisting construction · NCC 2019: Spec C1.1: 2.8

Open S5C9 on NCC Online ↗

(1) A Class 7 part of a building may be regarded as Class 2 for the purpose of determining the relevant fire-resisting requirements of this Specification where—

the entire building—

consists only of Class 2 and Class 7; and

contains not more than 4 storeys; and

the Class 7 part—

is wholly within the same storey; and

has a purpose that is ancillary to the building, such as carparking; and

is the only Class 7 part within the entire building.

(2) A Class 7 part of a building may be regarded as Class 3 for the purpose of determining the relevant fire-resisting requirements of this Specification where—

the entire building—

consists only of Class 3 and Class 7; and

contains not more than 3 storeys; and

the Class 7 part—

is wholly within the same storey; and

has a purpose that is ancillary to the building, such as carparking; and

is the only Class 7 part within the entire building.

Applications

For S5C9(2), reference to ‘Class 3’ may include Class 2 parts in conjunction with Class 3 parts.

Changed since NCC 2022. See NCC 2022 Volume One S5C9, or show what changed.

(1) If a Class 2 building contains not more than 4 storeys of which — one storey is A Class 7 used solely for the purpose part of parking motor vehicles or for some other purpose that is ancillary to a Class 2; and the remaining storeys are of Class 2, the carpark storey is building may be regarded as Class 2 only for the purpose of determining the relevant fire-resisting requirements of this Specification. (2) If a Class 3 Specification where — the entire building or a building — consists only of Class 2 and 3 Class 7; and contains not more than 3 storeys of which — one storey is 4 storeys; and the Class 7 used solely for part — is wholly within the purpose of parking motor vehicles or for some other same storey; and has a purpose that is ancillary to the other storeys; building, such as carparking; and is the remaining storeys are only Class 7 part within the entire building. (2) A Class 7 part of Class 2 or 3, the carpark storey is a building may be regarded as Class 2 or 3 only for the purpose of determining the relevant fire-resisting requirements of this Specification. Specification where — the entire building — consists only of Class 3 and Class 7; and contains not more than 3 storeys; and the Class 7 part — is wholly within the same storey; and has a purpose that is ancillary to the building, such as carparking; and is the only Class 7 part within the entire building. Applications For S5C9(2), reference to ‘Class 3’ may include Class 2 parts in conjunction with Class 3 parts.

Removed words are struck through; added words are highlighted. Comparison of the text only.