Specification clause · NCC 2025 Volume One

S5C12 Type A fire-resisting construction — concessions for floors

Specification 5 Fire-resisting construction · NCC 2019: Spec C1.1: 3.2

Open S5C12 on NCC Online ↗

A floor need not comply with Table S5C11g if—

it is laid directly on the ground; or

in a Class 2, 3, 5 or 9 building, the space below is not a storey, does not accommodate motor vehicles, is not a storage or work area, and is not used for any other ancillary purpose; or

it is a timber stage floor in a Class 9b building laid over a floor having the required FRL and the space below the stage is not used as a dressing room, store room, or the like; or

it is within a sole-occupancy unit in a Class 2 or 3 building or Class 4 part of a building; or

it is an open-access floor (for the accommodation of electrical and electronic services and the like) above a floor with the required FRL.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S5C12.