Specification clause · NCC 2025 Volume One

S5C11 Type A fire-resisting construction — fire-resistance of building elements

Specification 5 Fire-resisting construction · NCC 2019: Spec C1.1: 3.1 and Table 3

Open S5C11 on NCC Online ↗

(1) In a building required to be of Type A construction—

each building element listed in Tables S5C11a, S5C11b, S5C11c, S5C11d, S5C11e, S5C11f and S5C11g, and any beam or column incorporated in it, must have an FRL not less than that listed in those Tables for the particular class of building concerned; and

any internal wall required to have an FRL with respect to integrity and insulation must extend to—

the underside of the floor next above; or

the underside of a roof complying with Table S5C11g; or

if under S5C15 the roof is not required to comply with Table S5C11g, the underside of the non-combustible roof covering and, except for roof battens with dimensions of 75 mm x 50 mm or less or sarking-type material, must not be crossed by timber or other combustible building elements; or

a ceiling that is immediately below the roof and has a resistance to the incipient spread of fire to the roof space between the ceiling and the roof of not less than 60 minutes; and

a load bearing internal wall and a load bearing fire wall (including those that are part of a load bearing shaft) must be constructed from—

concrete; or

masonry; or

subject to (2), fire-protected timber; or

subject to (3), fire-protected steel; or

any combination of (i) to (iv); and

the FRLs specified in Table S5C11c for an external column apply also to those parts of an internal column that face and are within 1.5 m of a window and are exposed through that window to a fire-source feature.

(2) For the purposes of (1)(c)(iii), fire-protected timber may be used, provided that—

the building is—

a separate building; or

a part of a building—

which only occupies part of a storey, and is separated from the remaining part by a fire wall; or

which is located above or below a part not containing fire-protected timber and the floor between the adjoining parts is provided with an FRL not less than that prescribed for a fire wall for the lower storey; and

the building has an effective height of not more than 25 m; and

the building has a sprinkler system (other than a FPAA101D or FPAA101H system) throughout complying with Specification 17; and

any insulation installed in the cavity of the timber building element required to have an FRL is non-combustible; and

cavity barriers are provided in accordance with Specification 9.

(3) For the purposes of (1)(c)(iv), fire-protected steel may be used in a Class 2 or 3 building or the uppermost storey of any other building classification, provided that—

the building is—

a separate building; or

a part of a building—

which only occupies part of a storey, and is separate from the remaining part by a fire wall; or

which is located above a part not containing fire-protected steel and the floor between adjoining parts is provided with an FRL, not less than that prescribed for a fire wall for the lower storey; and

the building has an effective height of not more than 25 m; and

the building has a sprinkler system (other than a FPAA101D or FPAA101H system) throughout complying with Specification 17; and

any insulation installed in the cavity of walls required to have an FRL is non-combustible; and

at each floor level, any cavity within a wall required to have an FRL that provides a vertically continuous gap to the level above is interrupted by a cavity barrier in the form of a steel member, steel sheet of 0.5 mm base metal thickness or greater, a 16 mm thick or greater fire-protective grade plasterboard or a 45 mm thick or greater mineral wool barrier.

(4) For the purposes of Table S5C11a and Table S5C11b, external wall includes any column and other building element incorporated within it or other external building element.

Table S5C11a Type A construction: FRL of loadbearing parts of external walls

Distance from a fire-source feature

FRL (in minutes): Structural adequacy / Integrity / Insulation

Class 2, 3 or 4 part

Class 5, 7a or 9

Class 6

Class 7b or 8

Less than 1.5 m

90/90/90

120/120/120

180/180/180

240/240/240

1.5 to less than 3 m

90/60/60

120/90/90

180/180/120

240/240/180

3 m or more

90/60/30

120/60/30

180/120/90

240/180/90

Table S5C11b Type A construction: FRL of non-loadbearing parts of external walls

Distance from a fire-source feature

FRL (in minutes): Structural adequacy / Integrity / Insulation

Class 2, 3 or 4 part

Class 5, 7a or 9

Class 6

Class 7b or 8

Less than 1.5 m

–/90/90

–/120/120

–/180/180

–/240/240

1.5 to less than 3 m

–/60/60

–/90/90

–/180/120

–/240/180

3 m or more

–/–/–

–/–/–

–/–/–

–/–/–

Table S5C11c Type A construction: FRL of external columns not incorporated in an external wall

Column type

FRL (in minutes): Structural adequacy / Integrity / Insulation

Class 2, 3 or 4 part

Class 5, 7a or 9

Class 6

Class 7b or 8

Load bearing

90/–/–

120/–/–

180/–/–

240/–/–

Non-load bearing

–/–/–

–/–/–

–/–/–

–/–/–

Table S5C11d Type A construction: FRL of common walls and fire walls

Wall type

FRL (in minutes): Structural adequacy / Integrity / Insulation

Class 2, 3 or 4 part

Class 5, 7a or 9

Class 6

Class 7b or 8

Load bearing or non-load bearing

90/90/90

120/120/120

180/180/180

240/240/240

Table S5C11e Type A construction: FRL of loadbearing internal walls

Location

FRL (in minutes): Structural adequacy / Integrity / Insulation

Class 2, 3 or 4 part

Class 5, 7a or 9

Class 6

Class 7b or 8

Fire-resisting lift and stair shafts

90/90/90

120/120/120

180/120/120

240/120/120

Bounding public corridors, public lobbies and the like

90/90/90

120/–/–

180/–/–

240/–/–

Between or bounding sole-occupancy units

90/90/90

120/–/–

180/–/–

240/–/–

Ventilating, pipe, garbage, and like shafts not used for the discharge of hot products of combustion

90/90/90

120/90/90

180/120/120

240/120/120

Table S5C11f Type A construction: FRL of non-loadbearing internal walls

Location

FRL (in minutes): Structural adequacy / Integrity / Insulation

Class 2, 3 or 4 part

Class 5, 7a or 9

Class 6

Class 7b or 8

Fire-resisting lift and stair shafts

–/90/90

–/120/120

–120/120

–/120/120

Bounding public corridors, public lobbies and the like

–/60/60

–/–/–

–/–/–

–/–/–

Between or bounding sole-occupancy units

–/60/60

–/–/–

–/–/–

–/–/–

Ventilating, pipe, garbage, and like shafts not used for the discharge of hot products of combustion

–/90/90

–/90/90

–/120/120

–/120/120

Table S5C11g Type A construction: FRL of other building elements not covered by Tables S5C11a to S5C11f

Building element

FRL (in minutes): Structural adequacy / Integrity / Insulation

Class 2, 3 or 4 part

Class 5, 7a or 9

Class 6

Class 7b or 8

Other load bearing internal walls, internal beams, trusses and columns

90/–/–

120/–/–

180/–/–

240/–/–

Floors

90/90/90

120/120/120

180/180/180

240/240/240

Roofs

90/60/30

120/60/30

180/60/30

240/90/60

Tables

Changed since NCC 2022. See NCC 2022 Volume One S5C11, or show what changed.

(1) In a building required to be of Type A … the roof of not less than 60 minutes; and a loadbearing load bearing internal wall and a loadbearing load bearing fire wall (including those that are part of a loadbearing load bearing shaft) must be constructed from — concrete; or masonry; or subject to (2), fire-protected timber; or subject to (3), fire-protected steel; or any combination of (i) to (iii); (iv); and the FRLs specified in Table S5C11c for an external … in accordance with Specification 9. (3) For the purposes of (1)(c)(iv), fire-protected steel may be used in a Class 2 or 3 building or the uppermost storey of any other building classification, provided that — the building is — a separate building; or a part of a building — which only occupies part of a storey, and is separate from the remaining part by a fire wall; or which is located above a part not containing fire-protected steel and the floor between adjoining parts is provided with an FRL, not less than that prescribed for a fire wall for the lower storey; and the building has an effective height of not more than 25 m; and the building has a sprinkler system (other than a FPAA101D or FPAA101H system) throughout complying with Specification 17; and any insulation installed in the cavity of walls required to have an FRL is non-combustible; and at each floor level, any cavity within a wall required to have an FRL that provides a vertically continuous gap to the level above is interrupted by a cavity barrier in the form of a steel member, steel sheet of 0.5 mm base metal thickness or greater, a 16 mm thick or greater fire-protective grade plasterboard or a 45 mm thick or greater mineral wool barrier. (4) For the purposes of Table S5C11a and Table S5C11b, external wall includes any column … walls Distance from a fire-source feature FRL (in minutes): Structural adequacy/ adequacy / Integrity / Insulation Class 2, 3 or 4 part Class … 5, 7a or 9 Class 6 Class 7b or 8 Loadbearing Load bearing 90/–/– 120/–/– 180/–/– 240/–/– Non-loadbearing Non-load bearing –/–/– –/–/– –/–/– –/–/– Table S5C11d Type A construction: FRL … 5, 7a or 9 Class 6 Class 7b or 8 Loadbearing Load bearing or non-loadbearing non-load bearing 90/90/90 120/120/120 180/180/180 240/240/240 Table S5C11e Type A construction: FRL … 7a or 9 Class 6 Class 7b or 8 Other loadbearing load bearing internal walls, internal beams, trusses and columns 90/–/– 120/–/– 180/–/– 240/–/– Floors 90/90/90 120/120/120 180/180/180 240/240/240 Roofs 90/60/30 120/60/30 180/60/30 240/90/60

Removed words are struck through; added words are highlighted. Comparison of the text only.