S5C25 Type C fire-resisting construction — carparks
Specification 5 Fire-resisting construction · NCC 2019: Spec C1.1: 5.2 and Table 5.2
(1) Notwithstanding S5C24, a carpark may comply with this clause if it is an open-deck carpark or is protected with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 and is—
a separate building; or
a part of a building, and if occupying only part of a storey, is separated from the remaining part by a fire wall.
(2) For the purposes of this clause, a carpark —
includes—
an administration area associated with the functioning of the carpark; and
where the carpark is sprinklered, is associated with a Class 2 or 3 building and provides carparking for separate sole-occupancy units, each carparking area with an area not greater than 10% of its floor area for purposes ancillary to the sole-occupancy units; but
excludes—
except for (a), any area of another classification, or other part of a Class 7 building not used for carparking; and
a building or part of a building specifically intended for the parking of trucks, buses, vans and the like.
(3) For building elements in a carpark as described in (1) and (2), the following minimum FRLs are applicable:
External walls:
Less than 1.5 m from a fire-source feature to which it is exposed:
Load bearing: 60/60/60.
Non-load bearing: –/60/60.
1.5 m or more from a fire-source feature to which it is exposed: –/–/–.
Internal walls: –/–/–.
Fire walls:
From the direction used as a carpark: 60/60/60.
From the direction not used as a carpark: 90/90/90.
Columns:
Steel column less than 1.5 m from a fire-source feature —
60/–/–; or
ESA/M not greater than 26 m2/tonne.
Any other column not less than 1.5 m from a fire-source feature: 60/–/–.
Any other column not covered by (i) or (ii): –/–/–.
Beams:
Steel floor beam, less than 1.5 m from a fire-source feature, in continuous contact with a concrete floor slab—
60/–/–; or
an ESA/M of not greater than 30 m2/tonne.
any other beam: 60/–/–.
more than 1.5 m from a fire-source feature: –/–/–.
Roof, floor slab and vehicle ramp: –/–/–.
(4) For the purposes of (3), ESA/M means the ratio of exposed surface area to mass per unit length.