Specification clause · NCC 2025 Volume One

S5C6 General concessions

Specification 5 Fire-resisting construction · NCC 2019: Spec C1.1: 2.5

Open S5C6 on NCC Online ↗

(1) Steel columns — A steel column, other than one in a fire wall or common wall, need not have an FRL in a building that contains—

only 1 storey; or

2 storeys in some of its parts and 1 storey only in its remaining parts if the sum of the floor areas of the upper storeys of its 2 storey parts does not exceed the lesser of—

1/8 of the sum of the floor areas of the 1 storey parts; or

in the case of a building to which one of the maximum floor areas specified in Table C3D3 is applicable — 1/10 of that area; or

in the case of a building to which two or more of the maximum floor area specified in Table C3D3 is applicable — 1/10 of the lesser of those areas.

(2) Timber columns — A timber column may be used in a single storey building if—

in a fire wall or common wall the column has an FRL not less than that listed in Table S5C11d, S5C21d or S5C24c as appropriate; and

in any other case where the column is required to have an FRL in accordance with Table S5C11a, S5C11c, S5C11g, S5C21a, S5C21c, S5C21g, S5C24a or S5C24b, it has an FRL of not less than 30/–/–.

(3) Structures on roofs — A non-combustible structure situated on a roof need not comply with the other provisions of this Specification if it only contains—

lift motor equipment; or

one or more of the following:

Hot water or other water tanks.

Ventilating ductwork, ventilating fans and their motors.

Air-conditioning chillers.

Window cleaning equipment.

Other service units that are non-combustible and do not contain flammable or combustible liquids or gases.

(4) Curtain walls and panel walls — A requirement for an external wall to have an FRL does not apply to a curtain wall or panel wall which is of non-combustible construction and fully protected by automatic external wall-wetting sprinklers.

(5) Balconies and verandahs — A balcony, verandah or the like and any incorporated supporting part, which is attached to or forms part of a building, need not comply with Table S5C11c, S5C11g, S5C21c, S5C21g, S5C24b or S5C24e if—

it does not form part of the only path of travel to a required exit from the building; and

in Type A construction—

it is situated not more than 2 storeys above the lowest storey providing direct egress to a road or open space; and

any supporting columns are of non-combustible construction.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S5C6.