SA I4D5 Provision for escape
SA Part I4 Bulk grain storage facilities
Delete clause I4D5 and insert SA I4D5 as follows:
(1) In addition to any horizontal exit, not less than 2 exits must be provided from—
a storage shed in a bulk grain storage facility if the distance of travel to an exit is more than 150 m; and
the gallery level in a cell type silo in a bulk grain storage facility.
(2) A stairway or ramp serving as a required exit from a bulk grain storage facility is not required to be fire-isolated where there are no window or door openings within 3 m of the stairway, ramp or ladder.
(3) Where required exits are spaced not more than 100 m apart in a bulk grain storage facility, the travel distance to an exit in a cell type silo or storage shed is not limited to D2D5(3).
(4) In a bulk grain storage facility, the distance from any point on the floor to a point of egress to a road or open space by way of a non-fire-isolated stairway, non-fire-isolated ramp or ladder is not limited.
(5) A stair or ladder complying with AS 1657 may be used in a bulk grain storage facility as an alternative means of egress from a cell type silo.