Deemed-to-Satisfy Provision · NCC 2025 Volume One

F4D4 Facilities in Class 3 to 9 buildings

Part F4 Sanitary and other facilities · NCC 2019: F2.3

Open F4D4 on NCC Online ↗
Varied in NT, TAS, VIC. Check the variation for your state.

(1) Except where permitted by (3), (4), (7), (12), F4D5(a), F4D5(b) and F4D12(1), separate sanitary facilities for males and females must be provided for Class 3, 5, 6, 7, 8 or 9 buildings in accordance with Tables F4D4a, F4D4b, F4D4c, F4D4d, F4D4e, F4D4f, F4D4g, F4D4h, F4D4i, F4D4j, F4D4k and F4D4l, as appropriate.

(2) In Tables F4D4a, F4D4b, F4D4c, F4D4d, F4D4e, F4D4f, F4D4g, F4D4h, F4D4i, F4D4j, F4D4k and F4D4l —

‘Number’ means the number of facilities required; and

‘>’ means greater than; and

a hyphen means no data (refer to the row above for the highest value applicable); and

‘N/A’ means not applicable; and

a reference to—

‘employees’ includes owners and managers using the building; and

‘add 1 per 100 or 150, 250, 500, etc.’ includes any part thereof of that number.

(3) If not more than 10 people are employed, a unisex facility may be provided instead of separate facilities for each sex.

(4) If the majority of employees are of one sex, not more than 2 employees of the other sex may share toilet facilities if the facilities are separated by means of walls, partitions and doors to afford privacy.

(5) Employees and the public may share the same facilities in a Class 6 and 9b building (other than a school or early childhood centre) provided the number of facilities provided is not less than the total number of facilities required for employees plus those required for the public.

(6) Sanitary facilities must comply with the following:

In all sanitary facilities, adequate means of disposal of sanitary products must be provided.

In sanitary facilities for use by females, a dispenser for sanitary products must be provided.

(7) Separate sanitary facilities for males and females need not be provided for patients in a ward area of a Class 9a building.

(8) A Class 9a health-care building must be provided with—

one kitchen or other adequate facility for the preparation and cooking or reheating of food including a kitchen sink and washbasin; and

laundry facilities for the cleansing and drying of linen and clothing or adequate facilities for holding and dispatch or treatment of soiled linen and clothing, sanitary products and the like and the receipt and storage of clean linen; and

one shower for each 8 patients or part thereof; and

one island-type plunge bath in each storey containing a ward area.

(9) A Class 9b early childhood centre must be provided with—

a kitchen or food preparation area with a kitchen sink, separate hand washing facilities, space for a refrigerator and space for cooking facilities, with—

the facilities protected by a door or gate with child proof latches to prevent unsupervised access to the facilities by children younger than 5 years old; and

the ability to facilitate supervision of children from the facilities if the early childhood centre accommodates children younger than 2 years old; and

one bath, shower or shower-bath; and

if the centre accommodates children younger than 3 years old—

a laundry facility comprising a washtub and space in the same room for a washing machine; and

a bench type baby bath, which is within 1 m of the nappy change bench; and

a nappy changing bench which—

is within 1 m of separate adult hand washing facilities and bench type baby bath; and

must be not less than 0.9 m2 in area and at a height of not less than 850 mm, but not more than 900 mm above the finished floor level; and

must have a space not less than 800 mm high, 500 mm wide and 800 mm deep for the storage of steps; and

is positioned to permit a staff member changing a nappy to have visibility of the play area at all times.

(10) Class 9b theatres and sporting venues must be provided with one shower for each 10 participants or part thereof.

(11) Not less than one washbasin must be provided where closet pans or urinals are provided.

(12) All gender sanitary facilities may be provided in lieu of sanitary facilities for males and females provided in accordance with (1) in accordance with the following:

Where (1) requires in total 1 closet pan for males and 1 closet pan for females — all required closet pans and washbasins may be provided in all gender facilities.

Where (1) requires in total 3 closet pans or urinals — 1 closet pan may be provided in an all-gender facility where 1 closet pan is provided for use by males and 1 closet pan is provided for use by females.

Where (1) requires in total 4 or more closet pans or urinals — up to half of required closet pans or urinals for use by males and up to half of required closet pans for use by females may be provided in all gender facilities where the proportion of facilities deducted from males and the proportion of facilities deducted from females is equal.

Where (c) is applied, the number of washbasins required by (1) for use by males and females may be reduced by the proportion applied to closet pans and urinals

(13) For the purposes of this part, an all gender sanitary facility comprises 1 closet pan and 1 washbasin within the same compartment.

(14) An all gender sanitary facility must—

be located so that it can be entered without crossing an area reserved for one sex only; and

be identified by signage that states “all gender”.

Table F4D4a Sanitary facilities in Class 3, 5, 6 and 9 buildings other than schools

User group

Facility type

Design occupancy

Number

Male employees

Closet pans

1 - 20

1

>20

Add 1 per 20

Urinals

1 - 10

0

11 - 25

1

26 - 50

2

>50

Add 1 per 50

Washbasins

1 - 30

1

>30

Add 1 per 30

Female employees

Closet pans

1 - 15

1

>15

Add 1 per 15

Washbasins

1 - 30

1

>30

Add 1 per 30

Table F4D4b Sanitary facilities in Class 7 and 8 buildings

User group

Facility type

Design occupancy

Number

Male employees

Closet pans

1 - 20

1

>20

Add 1 per 20

Urinals

1 - 10

0

11 - 25

1

26 - 50

2

>50

Add 1 per 50

Washbasins

1 - 20

1

>20

Add 1 per 20

Female employees

Closet pans

1 - 15

1

>15

Add 1 per 15

Washbasins

1 - 20

1

>20

Add 1 per 20

Table Notes

Sanitary facilities need not be provided for a Class 8 electricity network substation.

Table F4D4c Sanitary facilities in Class 6 buildings – department stores, shopping centres

User group

Facility type

Design occupancy

Number

Male patrons

Closet pans

1 - 1200

1

>1200

Add 1 per 1200

Urinals

1 - 600

1

>600

Add 1 per 1200

Washbasins

1 - 600

1

>600

Add 1 per 1200

Female patrons

Closet pans

1 - 300

1

301 - 600

2

>600

Add 1 per 1200

Washbasins

1-600

1

601 - 1200

2

>1200

Add 1 per 1200

Table Notes

Sanitary facilities need not be provided for patrons if the total number of persons accommodated in the building is not more than 600.

Table F4D4d Sanitary facilities in Class 6 buildings – restaurants, cafes, bars

User group

Facility type

Design occupancy

Number

Male patrons

Closet pans

1 - 100

1

101 - 300

2

>300

Add 1 per 200

Urinals

1 - 50

1

51 - 100

2

101 - 150

3

151 - 200

4

201 - 250

5

>250

Add 1 per 100

Washbasins

1 - 50

1

51 - 200

2

>200

Add 1 per 200

Female patrons

Closet pans

1 - 25

1

26 - 50

2

51 - 100

3

101 - 150

4

151 - 200

5

201 - 250

6

>250

Add 1 per 100

Washbasins

1 - 50

1

51 - 150

2

>150

Add 1 per 200

Table Notes

Sanitary facilities need not be provided for patrons if the total number of persons accommodated in the building is not more than 20.

Table F4D4e Sanitary facilities in Class 9a health-care buildings

User group

Facility type

Design occupancy

Number

Male patients

Closet pans

1 - 16

2

>16

Add 1 per 8

Washbasins

1 - 8

1

>8

Add 1 per 8

Female patients

Closet pans

1 - 16

2

>16

Add 1 per 8

Washbasins

1 - 8

1

>8

Add 1 per 8

Table Notes

Urinals are not required for a Class 9a health-care building.

Table F4D4f Sanitary facilities in Class 9b buildings – schools

User group

Facility type

Design occupancy

Number

Male employees

Closet pans

1 - 20

1

>20

Add 1 per 20

Urinals

1 - 10

0

11 - 20

1

21 - 45

2

>45

Add 1 per 30

Washbasins

1 -30

1

>30

Add 1 per 30

Female employees

Closet pans

1 - 5

1

>5

Add 1 per 15

Washbasins

1 - 30

1

>30

Add 1 per 30

Male students

Closet pans

1 - 25

1

26 - 75

2

76 - 150

3

151 - 200

4

>200

Add 1 per 100

Urinals

1 - 50

1

51 - 100

2

>100

Add 1 per

Tables

Changed since NCC 2022. See NCC 2022 Volume One F4D4, or show what changed.

(1) Except where permitted by (3), (4), (7), (12), F4D5(a), F4D5(b) and F4D12(1), separate sanitary facilities for males and … required for employees plus those required for the public. (6) Adequate Sanitary facilities must comply with the following: In all sanitary facilities, adequate means of disposal of sanitary products must be provided in provided. In sanitary facilities for use by females. females, a dispenser for sanitary products must be provided. (7) Separate sanitary facilities for males and females need not … must be provided where closet pans or urinals are provided. (12) All gender sanitary facilities may be provided in lieu of sanitary facilities for males and females provided in accordance with (1) in accordance with the following: Where (1) requires in total 1 closet pan for males and 1 closet pan for females — all required closet pans and washbasins may be provided in all gender facilities. Where (1) requires in total 3 closet pans or urinals — 1 closet pan may be provided in an all-gender facility where 1 closet pan is provided for use by males and 1 closet pan is provided for use by females. Where (1) requires in total 4 or more closet pans or urinals — up to half of required closet pans or urinals for use by males and up to half of required closet pans for use by females may be provided in all gender facilities where the proportion of facilities deducted from males and the proportion of facilities deducted from females is equal. Where (c) is applied, the number of washbasins required by (1) for use by males and females may be reduced by the proportion applied to closet pans and urinals (13) For the purposes of this part, an all gender sanitary facility comprises 1 closet pan and 1 washbasin within the same compartment. (14) An all gender sanitary facility must — be located so that it can be entered without crossing an area reserved for one sex only; and be identified by signage that states “all gender”. Table F4D4a Sanitary facilities in Class 3, 5, 6 and … 50 1 51 - 100 2 >100 Add 1 per 100 Washbasins 1 - 10 1 11 - 50 2 51 - 100 3 >100 Add 1 per 75 Female students Closet pans 1 - 10 1 11 - 25 2 26 - 100 Add 1 per 25 >100 Add 1 per 50 Washbasins 1 - 10 1 11 - 50 2 51 - 100 3 >100 Add 1 per 75 Table F4D4g Sanitary facilities in Class 9b buildings – early childhood centres User group Facility type Design occupancy Number Children Closet pans 1 - 30 2 >30 Add 1 per 15 Washbasins 1 - 30 2 >30 Add 1 per 15 Table Notes Urinals are not required for a Class 9b early childhood centre. Facilities for use by children must be — junior pans; and washbasins with a rim height not exceeding 600 mm; and accessible from both indoor and outdoor play areas. Table F4D4h Sanitary facilities in Class 9b buildings – theatres and cinemas with multiple auditoria, art galleries and the like User group Facility type Design occupancy Number Male participants Closet pans 1 - 20 1 >20 Add 1 per 20 Urinals 1 - 10 1 >10 Add 1 per 10 Washbasins 1 - 10 1 >10 Add 1 per 10 Female participants Closet pans 1 - 10 1 >10 Add 1 per 10 Washbasins 1 - 10 1 >10 Add 1 per 10 Male spectators or patrons Closet pans 1 - 250 1 251 - 500 2 >500 Add 1 per 500 Urinals 1 - 100 1 >100 Add 1 per 100 Washbasins 1 - 150 1 >150 Add 1 per 150 Female spectators or patrons Closet pans 1 - 10 1 11 - 50 2 >50 Add 1 per 60 Washbasins 1 - 80 1 81 - 250 2 251 - 430 3 >430 Add 1 per 200 Table F4D4i Sanitary facilities in Class 9b buildings – single auditorium theatres and cinemas User group Facility type Design occupancy Number Male pat

Removed words are struck through; added words are highlighted. Comparison of the text only.

Can't meet F4D4? A Performance Solution must meet the Performance Requirements it satisfies: F4P1, F4P2, F4P3, F4P4, F4P5, F4P6. Start a Performance Solution →

State and territory variations all clauses side by side →