Table · NCC 2025 Volume One
Table F4D4l Sanitary facilities in Class 9b buildings – public halls, function rooms or the like
Part F4 Sanitary and other facilities
| User group | Facility type | Design occupancy | Number |
|---|---|---|---|
| Male patrons | Closet pans | 1 - 100 | 1 |
| >100 | Add 1 per 200 | ||
| Urinals | 1 - 50 | 1 | |
| 51 - 100 | 2 | ||
| 101 - 150 | 3 | ||
| 151 - 200 | 4 | ||
| 201 - 250 | 5 | ||
| >250 | Add 1 per 100 | ||
| Washbasins | 1 - 50 | 1 | |
| 51 - 200 | 2 | ||
| >200 | Add 1 per 200 | ||
| Female patrons | Closet pans | 1 - 25 | 1 |
| 26 - 50 | 2 | ||
| 51 - 100 | 3 | ||
| 101 - 150 | 4 | ||
| 151 - 200 | 5 | ||
| 201 - 250 | 6 | ||
| >250 | Add 1 per 100 | ||
| Washbasins | 1 - 50 | 1 | |
| 51 - 150 | 2 | ||
| >150 | Add 1 per 200 |
Table Notes
Sanitary facilities need not be provided for patrons if the total number of persons accommodated in the building is not more than 20.
Table for F4D4 Facilities in Class 3 to 9 buildings
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table F4D4l.