Table · NCC 2025 Volume One
Table J3D9 Maximum wall-glazing construction solar admittance
Part J3 Elemental provisions for a Class 4 part of a building
| Climate zone | Eastern aspect solar admittance | Northern aspect solar admittance | Southern aspect solar admittance | Western aspect solar admittance |
|---|---|---|---|---|
| 1 | 0.10 | 0.10 | 0.14 | 0.10 |
| 2 | 0.10 | 0.10 | 0.10 | 0.10 |
| 3 | 0.11 | 0.11 | 0.11 | 0.11 |
| 4 | 0.11 | 0.11 | 0.11 | 0.11 |
| 5 | 0.13 | 0.13 | 0.13 | 0.13 |
| 6 | 0.14 | 0.14 | 0.14 | 0.14 |
| 7 | N/A | N/A | N/A | N/A |
| 8 | N/A | N/A | N/A | N/A |
Table for J3D9 Wall-glazing construction of a Class 4 part of a building
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table J3D9.