J3D8 External walls of a Class 4 part of a building
Part J3 Elemental provisions for a Class 4 part of a building
(1) The Total R-Value of an external wall —
in climate zones 1, 2, 3, 5 and 6—
where the ratio of the area of opaque external walls to the floor area of the sole-occupancy unit is less than 20%, must be at least R1.15; and
where the ratio of the area of opaque external walls to the floor area of the sole-occupancy unit is greater than or equal to 20% but less than 35%, must be at least R2.04; and
where the ratio of the area of opaque external walls to the floor area of the sole-occupancy unit is greater than or equal to 35%, must be at least R2.24; and
in climate zones 4, 7 and 8, must be at least R2.24.
(2) The Total R-Value of an external wall must be determined in accordance with—
for a spandrel panel in a curtain wall system, in accordance with Specification 38; and
for all other walls, in accordance with AS/NZS 4859.2.
(3) The solar absorptance of an external wall must—
in climate zones 1 to 6, be in accordance with Table J3D8a; and
in climate zones 7 and 8, be in accordance with Table J3D8b.
Table J3D8a Solar absorptance – climate zones 1 to 6
Climate zone
Opaque external wall to net floor area ratio
Permitted solar absorptance
1 and 3
< 45%
≤ 0.8
≥ 45%
≤ 0.35
2
< 35%
Any
≥ 35%
Any, or ≤ 0.35, if shading device overhang is < 300 mm
4 and 5
< 45%
Any
≥ 45%
≤ 0.35, if shading device overhang is < 1500 mm
6
Any
Any
Table J3D8b Solar absorptance – climate zones 7 and 8
Opaque external wall to net floor area ratio
Shading device overhang (mm)
≥ 0 to < 600
≥ 600 to < 900
≥ 900 to < 1200
≥ 1200
< 20%
Any
Any
≥ 0.4
X
≥ 20% to < 35%
Any
Any
X
X
≥ 35% to < 45%
Any
≥ 0.4
X
X
≥ 45%
Any
≥ 0.6
X
X
Table Notes
X = not permitted
Tables
- Table J3D8a Solar absorptance – climate zones 1 to 6
- Table J3D8b Solar absorptance – climate zones 7 and 8