Table · NCC 2022 Volume One

Table J3D9 Maximum wall-glazing construction solar admittance

Part J3 Elemental provisions for a sole-occupancy unit of a Class 2 building or a Class 4 part of a building

Open Table J3D9 on NCC Online ↗
Climate zoneEastern aspect solar admittanceNorthern aspect solar admittanceSouthern aspect solar admittanceWestern aspect solar admittance
10.100.100.140.10
20.100.100.100.10
30.110.110.110.11
40.110.110.110.11
50.130.130.130.13
60.140.140.140.14
7N/AN/AN/AN/A
8N/AN/AN/AN/A

Table for J3D9 Wall-glazing construction of a sole-occupancy unit of a Class 2 building or a Class 4 part of a building

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table J3D9.