Table · NCC 2025 Volume One
Table J4D6c Maximum wall-glazing construction solar admittance - Class 5, 6, 7, 8 or 9b building or Class 9a building other than a ward area
| Climate zone | Eastern aspect solar admittance | Northern aspect solar admittance | Southern aspect solar admittance | Western aspect solar admittance |
|---|---|---|---|---|
| 1 to 7 | 0.10 | 0.09 | 0.11 | 0.09 |
| 8 | 0.10 | 0.10 | 0.20 | 0.10 |
Table for J4D6 Walls and glazing
Changed since NCC 2022. See NCC 2022 Volume One Table J4D6c, or show what changed.
Climate zone | Eastern aspect solar admittance | Northern aspect solar admittance | Southern aspect solar admittance | Western aspect solar admittance 1 | 0.07 | 0.07 to 7 | 0.10 | 0.07 2 0.09 | 0.11 | 0.09 8 | 0.10 | 0.10 | 0.10 0.20 | 0.10 3 | 0.07 | 0.07 | 0.07 | 0.07 4 | 0.07 | 0.07 | 0.07 | 0.07 5 | 0.10 | 0.10 | 0.10 | 0.10 6 | 0.07 | 0.07 | 0.07 | 0.07 7 | 0.07 | 0.07 | 0.08 | 0.07 8 | 0.08 | 0.08 | 0.08 | 0.08
Removed words are struck through; added words are highlighted. Comparison of the text only.