Table · NCC 2025 Volume One
Table J6D9a Piping — Minimum insulation R-Value
Part J6 Air-conditioning and ventilation
| Fluid temperature | Minimum insulation R-Value nominal pipe diameter ≤ 40 mm | Minimum insulation R-Value — nominal pipe diameter > 40 mm and ≤ 80 mm | Minimum insulation R-Value — nominal pipe diameter between > 80 mm and ≤ 150 mm | Minimum insulation R-Value — nominal pipe diameter > 150 mm |
|---|---|---|---|---|
| Low temperature chilled — ≤ 2°C | 1.3 | 1.7 | 2.0 | 2.7 |
| Chilled — > 2°C but ≤ 20°C | 1.0 | 1.5 | 2.0 | 2.0 |
| Heated — > 30°C but ≤ 85°C | 1.7 | 1.7 | 1.7 | 1.7 |
| High temperature heated — > 85°C | 2.7 | 2.7 | 2.7 | 2.7 |
Table Notes
The minimum required R-Value may be halved for piping penetrating a structural member.
Table for J6D9 Pipework insulation
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table J6D9a.