J6D9 Pipework insulation
Part J6 Air-conditioning and ventilation · NCC 2019: J5.8
(1) Piping, vessels, heat exchangers and tanks containing heating or cooling fluid, where the fluid is held at a heated or cooled temperature, that are part of an air-conditioning system, other than within appliances covered by MEPS, must be provided with insulation—
complying with AS/NZS 4859.1; and
for piping of heating and cooling fluids, having an insulation R-Value in accordance with Table J6D9a; and
for vessels, heat exchangers or tanks, having an insulation R-Value in accordance with Table J6D9b; and
for refill or pressure relief piping, having an insulation R-Value equal to the required insulation R-Value of the connected pipe, vessel or tank within 500 mm of the connection.
(2) Insulation must—
be protected against the effects of weather and sunlight; and
be able to withstand the temperatures within the piping, vessel, heat exchanger or tank.
(3) Insulation provided to piping, vessels, heat exchangers or tanks containing cooling fluid must be protected by a vapour barrier on the outside of the insulation.
(4) The requirements of (1) and (2) do not apply to piping, vessels or heat exchangers—
located within the only or last room served by the system and downstream of the control device for the regulation of heating or cooling service to that room; or
encased within a concrete slab or panel which is part of a heating or cooling system; or
supplied as an integral part of a chiller, boiler or unitary air-conditioner complying with the requirements of J6D10, J6D11 and J6D12; or
inside an air-handling unit, fan-coil unit, or the like.
(5) For the purposes of (1), (2), (3) and (4)—
heating fluids include heated water, steam and condensate; and
cooling fluids include refrigerant, chilled water, brines and glycol mixtures, but do not include condenser cooling water.
Table J6D9a Piping — Minimum insulation R-Value
Fluid temperature
Minimum insulation R-Value nominal pipe diameter ≤ 40 mm
Minimum insulation R-Value — nominal pipe diameter > 40 mm and ≤ 80 mm
Minimum insulation R-Value — nominal pipe diameter between > 80 mm and ≤ 150 mm
Minimum insulation R-Value — nominal pipe diameter > 150 mm
Low temperature chilled — ≤ 2°C
1.3
1.7
2.0
2.7
Chilled — > 2°C but ≤ 20°C
1.0
1.5
2.0
2.0
Heated — > 30°C but ≤ 85°C
1.7
1.7
1.7
1.7
High temperature heated — > 85°C
2.7
2.7
2.7
2.7
Table Notes
The minimum required R-Value may be halved for piping penetrating a structural member.
Table J6D9b Vessels, heat exchangers and tanks — Minimum insulation R-Value
Fluid temperature range
Minimum insulation R-Value
Low temperature chilled — ≤ 2°C
2.7
Chilled — > 2°C but ≤ 20°C
1.8
Heated — > 30°C but ≤ 85°C
3.0
High temperature heated — > 85°C
3.0
Tables
- Table J6D9a Piping — Minimum insulation R-Value
- Table J6D9b Vessels, heat exchangers and tanks — Minimum insulation R-Value
Changed since NCC 2022 (minor wording). See NCC 2022 Volume One J6D9, or show what changed.
(1) Piping, vessels, heat exchangers and tanks containing heating or … temperature, that are part of an air-conditioning system, other than in within appliances covered by MEPS, must be provided with insulation — … purposes of (1), (2), (3) and (4)— heating fluids include refrigerant, heated water, steam and condensate; and cooling fluids include refrigerant, … > 30°C but ≤ 85°C 1.7 1.7 1.7 1.7 High Temperature temperature heated — > 85°C 2.7 2.7 2.7 2.7 Table Notes … ≤ 85°C 3.0 High temperature heated — > 85°C 3.0
Removed words are struck through; added words are highlighted. Comparison of the text only.