Table · NCC 2025 Volume One

Table J9D4 Electric vehicle distribution board requirement for each storey of a carpark

Part J9 Energy monitoring and on-site distributed energy resources

Open Table J9D4 on NCC Online ↗
Carpark spaces per storey for electric vehiclesElectrical distribution boards required for electric vehicle charging per storey
0 - 90
10 - 241
25 - 482
49 - 723
73 - 964
97 - 1205
121 - 1446
145 - 1687

Table Notes

Where there are more than 168 carpark spaces per storey, one additional distribution board must be provided for each additional 24 spaces or part thereof.

The number of distribution boards required is determined by application of J9D4(2)(d).

Table for J9D4 Facilities for electric vehicle charging equipment

Changed since NCC 2022. See NCC 2022 Volume One Table J9D4, or show what changed.

Carpark spaces per storey for electric vehicles | Electrical distribution boards required for electric vehicle charging per storey 0 - 9 | … be provided for each additional 24 spaces or part thereof. The number of distribution boards required is determined by application of J9D4(2)(d).

Removed words are struck through; added words are highlighted. Comparison of the text only.