Table · NCC 2025 Volume One
Table S47C2a Load weighting factors - Class 5, 6, 7, 8 or 9b building or Class 9a building other than a ward area
Specification 47 Calculation of climate specific part load value for chillers
| Load | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 |
|---|---|---|---|---|---|---|---|---|
| 25% | 7% | 25% | 23% | 25% | 24% | 42% | 28% | 20% |
| 50% | 48% | 43% | 48% | 35% | 46% | 31% | 36% | 27% |
| 75% | 43% | 31% | 28% | 37% | 30% | 26% | 34% | 42% |
| 100% | 2% | 1% | 1% | 3% | 0% | 1% | 2% | 11% |
Table Notes
Load is the proportion of the total design load served by a connected group of chillers.
CZ = climate zone.
Table for S47C2 Calculation of climate specific part load value for chillers
New in NCC 2025. No Table S47C2a in NCC 2022 Volume One; it may have moved or been renumbered.