Table · NCC 2025 Volume One

Table S47C2a Load weighting factors - Class 5, 6, 7, 8 or 9b building or Class 9a building other than a ward area

Specification 47 Calculation of climate specific part load value for chillers

Open Table S47C2a on NCC Online ↗
LoadCZ 1CZ 2CZ 3CZ 4CZ 5CZ 6CZ 7CZ 8
25%7%25%23%25%24%42%28%20%
50%48%43%48%35%46%31%36%27%
75%43%31%28%37%30%26%34%42%
100%2%1%1%3%0%1%2%11%

Table Notes

Load is the proportion of the total design load served by a connected group of chillers.

CZ = climate zone.

Table for S47C2 Calculation of climate specific part load value for chillers

New in NCC 2025. No Table S47C2a in NCC 2022 Volume One; it may have moved or been renumbered.