Table · NCC 2025 Volume One

Table S47C2b Load weighting factors - Class 3 or 9c building or Class 9a ward area

Specification 47 Calculation of climate specific part load value for chillers

Open Table S47C2b on NCC Online ↗
LoadCZ 1CZ 2CZ 3CZ 4CZ 5CZ 6CZ 7CZ 8
25%7%31%23%43%41%60%40%16%
50%31%39%44%39%35%24%31%32%
75%61%28%32%18%23%15%26%49%
100%1%2%1%0%1%1%3%3%

Table Notes

Load is the proportion of the total design load served by a connected group of chillers.

CZ = climate zone.

Table for S47C2 Calculation of climate specific part load value for chillers

New in NCC 2025. No Table S47C2b in NCC 2022 Volume One; it may have moved or been renumbered.

Defined terms used