Table · NCC 2025 Volume One
Table S47C2b Load weighting factors - Class 3 or 9c building or Class 9a ward area
Specification 47 Calculation of climate specific part load value for chillers
| Load | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 |
|---|---|---|---|---|---|---|---|---|
| 25% | 7% | 31% | 23% | 43% | 41% | 60% | 40% | 16% |
| 50% | 31% | 39% | 44% | 39% | 35% | 24% | 31% | 32% |
| 75% | 61% | 28% | 32% | 18% | 23% | 15% | 26% | 49% |
| 100% | 1% | 2% | 1% | 0% | 1% | 1% | 3% | 3% |
Table Notes
Load is the proportion of the total design load served by a connected group of chillers.
CZ = climate zone.
Table for S47C2 Calculation of climate specific part load value for chillers
New in NCC 2025. No Table S47C2b in NCC 2022 Volume One; it may have moved or been renumbered.