NCC 2025 Volume One
Specification 47 Calculation of climate specific part load value for chillers
8 clauses · Open on NCC Online ↗
- S47C1 ScopeThis Specification contains the method to calculate the climate specific part load value for a connected group of chillers that serves a common…
- Table S47C2a Load weighting factors - Class 5, 6, 7, 8 or 9b building or Class 9a building other than a ward areaLoad | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 25% | 7% | 25% | 23% | 25% | 24% | 42% | 28% | 20% 50% | 48% | 43% | 48% | 35% | 46% |…
- Table S47C2b Load weighting factors - Class 3 or 9c building or Class 9a ward areaLoad | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 25% | 7% | 31% | 23% | 43% | 41% | 60% | 40% | 16% 50% | 31% | 39% | 44% | 39% | 35% |…
- Table S47C2c Part load evaluation points - outdoor wet bulb temperature (°C), Class 5, 6, 7, 8 or 9b building or Class 9a building other than a ward areaLoad | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 25% | 17 | 16 | 12 | 12 | 14 | 12 | 12 | 10 50% | 24 | 22 | 17 | 17 | 20 | 18 | 17 | 13…
- Table S47C2d Part load evaluation points - outdoor wet bulb temperature (°C), Class 3 or 9c building or Class 9a ward areaLoad | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 25% | 19 | 18 | 12 | 14 | 17 | 14 | 14 | 10 50% | 24 | 22 | 17 | 18 | 21 | 19 | 17 | 13…
- Table S47C2e Part load evaluation points - outdoor dry bulb temperature (°C), Class 5, 6, 7, 8 or 9b building or Class 9a building other than a ward areaLoad | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 25% | 27 | 21 | 21 | 18 | 19 | 17 | 17 | 14 50% | 31 | 27 | 32 | 27 | 25 | 26 | 25 | 20…
- Table S47C2f Part load evaluation points - outdoor dry bulb temperature (°C), Class 3 or 9c building or Class 9a ward areaLoad | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 25% | 24 | 22 | 21 | 20 | 21 | 19 | 18 | 14 50% | 29 | 27 | 31 | 29 | 26 | 27 | 26 | 17…
- S47C2 Calculation of climate specific part load value for chillersThe climate specific part load value for a group of one or more chillers must be calculated in accordance with the following formula: [formula]…