S47C2 Calculation of climate specific part load value for chillers
Specification 47 Calculation of climate specific part load value for chillers
(1) The climate specific part load value for a group of one or more chillers must be calculated in accordance with the following formula:
[formula] where—
[formula] = climate specific part load value; and
[formula] = the weighted average energy efficiency ratio of the chillers that operate to provide n% of the design cooling load under the staging strategy to be deployed, determined in accordance with (2) and (3); and
[formula] = load weighting factors specified in—
Table S47C2a for chillers serving a Class 5, 6, 7, 8 or 9b building or a Class 9a building other than a ward area; or
Table S47C2b for chillers serving a Class 3 or 9c building or a Class 9a ward area.
(2)
[formula] is determined as the weighted average energy efficiency ratio of the chillers operating to meet n% of the design cooling load under the staging strategy to be deployed, allowing for the part load efficiencies at—
a chilled water leaving temperature of 7°C; and
a chilled water flow rate that corresponds to a 6°C difference between entering and leaving temperatures at the rated cooling capacity, when determined in accordance with AHRI 551/591; and
for water-cooled chillers—
a condenser water entering temperature that is determined by adding the design approach temperature to the outside wet bulb temperature listed in—
Table S47C2c for chillers serving a Class 5, 6, 7, 8 or 9b building or a Class 9a building other than a ward area; or
Table S47C2d for chillers serving a Class 3 or 9c building or a Class 9a ward area; and
a condenser water flow rate that corresponds to a 6°C difference between entering and leaving temperature at the rated cooling capacity, when determined in accordance with AHRI 551/591; and
for air-cooled chillers, the outside dry bulb temperature listed in—
Table S47C2e for chillers serving a Class 5, 6, 7, 8 or 9b building or a Class 9a building other than a ward area; or
Table S47C2f for a Class 3 or 9c building or a Class 9a ward area.
(3)
The [formula] values in (2) must be determined using test measurements and calculations performed in accordance with the procedures of AHRI 551/591.
Table S47C2a Load weighting factors - Class 5, 6, 7, 8 or 9b building or Class 9a building other than a ward area
Load
CZ 1
CZ 2
CZ 3
CZ 4
CZ 5
CZ 6
CZ 7
CZ 8
25%
7%
25%
23%
25%
24%
42%
28%
20%
50%
48%
43%
48%
35%
46%
31%
36%
27%
75%
43%
31%
28%
37%
30%
26%
34%
42%
100%
2%
1%
1%
3%
0%
1%
2%
11%
Table Notes
Load is the proportion of the total design load served by a connected group of chillers.
CZ = climate zone.
Table S47C2b Load weighting factors - Class 3 or 9c building or Class 9a ward area
Load
CZ 1
CZ 2
CZ 3
CZ 4
CZ 5
CZ 6
CZ 7
CZ 8
25%
7%
31%
23%
43%
41%
60%
40%
16%
50%
31%
39%
44%
39%
35%
24%
31%
32%
75%
61%
28%
32%
18%
23%
15%
26%
49%
100%
1%
2%
1%
0%
1%
1%
3%
3%
Table Notes
Load is the proportion of the total design load served by a connected group of chillers.
CZ = climate zone.
Table S47C2c Part load evaluation points - outdoor wet bulb temperature (°C), Class 5, 6, 7, 8 or 9b building or Class 9a building other than a ward area
Load
CZ 1
CZ 2
CZ 3
CZ 4
CZ 5
CZ 6
CZ 7
CZ 8
25%
17
16
12
12
14
12
12
10
50%
24
22
17
17
20
18
17
13
75%
27
25
21
20
23
20
19
15
100%
28
27
23
22
25
24
21
14
Table Notes
Load is the proportion of the total design load served by a connected group of chillers.
CZ = climate zone.
Table S47C2d Part load evaluation points - outdoor wet bulb temperature (°C), Class 3 or 9c building or Class 9a ward area
Load
CZ 1
CZ 2
CZ 3
CZ 4
CZ 5
CZ 6
CZ 7
CZ 8
25%
19
18
12
14
17
14
14
10
50%
24
22
17
18
21
19
17
13
75%
27
25
20
20
23
21
19
14
100%
29
27
24
23
26
23
20
17
Table Notes
Load is proportion of the total design load served by a connected group of chillers.
CZ = climate zone.
Table S47C2e Part load evaluation points - outdoor dry bulb temperature (°C), Class 5, 6, 7, 8 or 9b building or Class 9a building other than a ward area
Load
CZ 1
CZ 2
CZ 3
CZ 4
CZ 5
CZ 6
CZ 7
CZ 8
25%
27
21
21
18
19
17
17
14
50%
31
27
32
27
25
26
25
20
75%
32
29
34
31
28
31
29
23
100%
29
29
28
32
27
36
32
25
Table Notes
Load is the proportion of the total design load served by a connected group of chillers.
CZ = climate zone.
Table S47C2f Part load evaluation points - outdoor dry bulb temperature (°C), Class 3 or 9c building or Class 9a ward area
Load
CZ 1
CZ 2
CZ 3
CZ 4
CZ 5
CZ 6
CZ 7
CZ 8
25%
24
22
21
20
21
19
18
14
50%
29
27
31
29
26
27
26
17
75%
31
29
36
34
29
33
31
22
100%
34
32
39
41
32
41
36
27
Table Notes
Load is the proportion of the total design load served by a connected group of chillers.
CZ = climate zone.
Tables
- Table S47C2a Load weighting factors - Class 5, 6, 7, 8 or 9b building or Class 9a building other than a ward area
- Table S47C2b Load weighting factors - Class 3 or 9c building or Class 9a ward area
- Table S47C2c Part load evaluation points - outdoor wet bulb temperature (°C), Class 5, 6, 7, 8 or 9b building or Class 9a building other than a ward area
- Table S47C2d Part load evaluation points - outdoor wet bulb temperature (°C), Class 3 or 9c building or Class 9a ward area
- Table S47C2e Part load evaluation points - outdoor dry bulb temperature (°C), Class 5, 6, 7, 8 or 9b building or Class 9a building other than a ward area
- Table S47C2f Part load evaluation points - outdoor dry bulb temperature (°C), Class 3 or 9c building or Class 9a ward area