S47C2 Calculation of climate specific part load value for chillers

Specification 47 Calculation of climate specific part load value for chillers

Open S47C2 on NCC Online ↗

(1) The climate specific part load value for a group of one or more chillers must be calculated in accordance with the following formula:

[formula] where—

[formula] = climate specific part load value; and

[formula] = the weighted average energy efficiency ratio of the chillers that operate to provide n% of the design cooling load under the staging strategy to be deployed, determined in accordance with (2) and (3); and

[formula] = load weighting factors specified in—

Table S47C2a for chillers serving a Class 5, 6, 7, 8 or 9b building or a Class 9a building other than a ward area; or

Table S47C2b for chillers serving a Class 3 or 9c building or a Class 9a ward area.

(2)

[formula] is determined as the weighted average energy efficiency ratio of the chillers operating to meet n% of the design cooling load under the staging strategy to be deployed, allowing for the part load efficiencies at—

a chilled water leaving temperature of 7°C; and

a chilled water flow rate that corresponds to a 6°C difference between entering and leaving temperatures at the rated cooling capacity, when determined in accordance with AHRI 551/591; and

for water-cooled chillers—

a condenser water entering temperature that is determined by adding the design approach temperature to the outside wet bulb temperature listed in—

Table S47C2c for chillers serving a Class 5, 6, 7, 8 or 9b building or a Class 9a building other than a ward area; or

Table S47C2d for chillers serving a Class 3 or 9c building or a Class 9a ward area; and

a condenser water flow rate that corresponds to a 6°C difference between entering and leaving temperature at the rated cooling capacity, when determined in accordance with AHRI 551/591; and

for air-cooled chillers, the outside dry bulb temperature listed in—

Table S47C2e for chillers serving a Class 5, 6, 7, 8 or 9b building or a Class 9a building other than a ward area; or

Table S47C2f for a Class 3 or 9c building or a Class 9a ward area.

(3)

The [formula] values in (2) must be determined using test measurements and calculations performed in accordance with the procedures of AHRI 551/591.

Table S47C2a Load weighting factors - Class 5, 6, 7, 8 or 9b building or Class 9a building other than a ward area

Load

CZ 1

CZ 2

CZ 3

CZ 4

CZ 5

CZ 6

CZ 7

CZ 8

25%

7%

25%

23%

25%

24%

42%

28%

20%

50%

48%

43%

48%

35%

46%

31%

36%

27%

75%

43%

31%

28%

37%

30%

26%

34%

42%

100%

2%

1%

1%

3%

0%

1%

2%

11%

Table Notes

Load is the proportion of the total design load served by a connected group of chillers.

CZ = climate zone.

Table S47C2b Load weighting factors - Class 3 or 9c building or Class 9a ward area

Load

CZ 1

CZ 2

CZ 3

CZ 4

CZ 5

CZ 6

CZ 7

CZ 8

25%

7%

31%

23%

43%

41%

60%

40%

16%

50%

31%

39%

44%

39%

35%

24%

31%

32%

75%

61%

28%

32%

18%

23%

15%

26%

49%

100%

1%

2%

1%

0%

1%

1%

3%

3%

Table Notes

Load is the proportion of the total design load served by a connected group of chillers.

CZ = climate zone.

Table S47C2c Part load evaluation points - outdoor wet bulb temperature (°C), Class 5, 6, 7, 8 or 9b building or Class 9a building other than a ward area

Load

CZ 1

CZ 2

CZ 3

CZ 4

CZ 5

CZ 6

CZ 7

CZ 8

25%

17

16

12

12

14

12

12

10

50%

24

22

17

17

20

18

17

13

75%

27

25

21

20

23

20

19

15

100%

28

27

23

22

25

24

21

14

Table Notes

Load is the proportion of the total design load served by a connected group of chillers.

CZ = climate zone.

Table S47C2d Part load evaluation points - outdoor wet bulb temperature (°C), Class 3 or 9c building or Class 9a ward area

Load

CZ 1

CZ 2

CZ 3

CZ 4

CZ 5

CZ 6

CZ 7

CZ 8

25%

19

18

12

14

17

14

14

10

50%

24

22

17

18

21

19

17

13

75%

27

25

20

20

23

21

19

14

100%

29

27

24

23

26

23

20

17

Table Notes

Load is proportion of the total design load served by a connected group of chillers.

CZ = climate zone.

Table S47C2e Part load evaluation points - outdoor dry bulb temperature (°C), Class 5, 6, 7, 8 or 9b building or Class 9a building other than a ward area

Load

CZ 1

CZ 2

CZ 3

CZ 4

CZ 5

CZ 6

CZ 7

CZ 8

25%

27

21

21

18

19

17

17

14

50%

31

27

32

27

25

26

25

20

75%

32

29

34

31

28

31

29

23

100%

29

29

28

32

27

36

32

25

Table Notes

Load is the proportion of the total design load served by a connected group of chillers.

CZ = climate zone.

Table S47C2f Part load evaluation points - outdoor dry bulb temperature (°C), Class 3 or 9c building or Class 9a ward area

Load

CZ 1

CZ 2

CZ 3

CZ 4

CZ 5

CZ 6

CZ 7

CZ 8

25%

24

22

21

20

21

19

18

14

50%

29

27

31

29

26

27

26

17

75%

31

29

36

34

29

33

31

22

100%

34

32

39

41

32

41

36

27

Table Notes

Load is the proportion of the total design load served by a connected group of chillers.

CZ = climate zone.