Table · NCC 2025 Volume One

Table S47C2f Part load evaluation points - outdoor dry bulb temperature (°C), Class 3 or 9c building or Class 9a ward area

Specification 47 Calculation of climate specific part load value for chillers

Open Table S47C2f on NCC Online ↗
LoadCZ 1CZ 2CZ 3CZ 4CZ 5CZ 6CZ 7CZ 8
25%2422212021191814
50%2927312926272617
75%3129363429333122
100%3432394132413627

Table Notes

Load is the proportion of the total design load served by a connected group of chillers.

CZ = climate zone.

Table for S47C2 Calculation of climate specific part load value for chillers

New in NCC 2025. No Table S47C2f in NCC 2022 Volume One; it may have moved or been renumbered.