Table S47C2f Part load evaluation points - outdoor dry bulb temperature (°C), Class 3 or 9c building or Class 9a ward area
Specification 47 Calculation of climate specific part load value for chillers
| Load | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 |
|---|---|---|---|---|---|---|---|---|
| 25% | 24 | 22 | 21 | 20 | 21 | 19 | 18 | 14 |
| 50% | 29 | 27 | 31 | 29 | 26 | 27 | 26 | 17 |
| 75% | 31 | 29 | 36 | 34 | 29 | 33 | 31 | 22 |
| 100% | 34 | 32 | 39 | 41 | 32 | 41 | 36 | 27 |
Table Notes
Load is the proportion of the total design load served by a connected group of chillers.
CZ = climate zone.
Table for S47C2 Calculation of climate specific part load value for chillers