Table · NCC 2025 Volume One

Table S47C2e Part load evaluation points - outdoor dry bulb temperature (°C), Class 5, 6, 7, 8 or 9b building or Class 9a building other than a ward area

Specification 47 Calculation of climate specific part load value for chillers

Open Table S47C2e on NCC Online ↗
LoadCZ 1CZ 2CZ 3CZ 4CZ 5CZ 6CZ 7CZ 8
25%2721211819171714
50%3127322725262520
75%3229343128312923
100%2929283227363225

Table Notes

Load is the proportion of the total design load served by a connected group of chillers.

CZ = climate zone.

Table for S47C2 Calculation of climate specific part load value for chillers

New in NCC 2025. No Table S47C2e in NCC 2022 Volume One; it may have moved or been renumbered.