S5C21 Type B fire-resisting construction — fire-resistance of building elements
Specification 5 Fire-resisting construction · NCC 2019: Spec C1.1: 4.1 and Table 4
(1) In a building required to be of Type B construction—
each building element listed in Tables S5C21a, S5C21b, S5C21c, S5C21d, S5C21e, S5C21f and S5C21g, and any beam or column incorporated in it, must have an FRL not less than that listed in the Tables for the particular class of building concerned; and
if a stair shaft supports any floor or a structural part of it—
the floor or part must have an FRL of 60/–/– or more; or
the junction of the stair shaft must be constructed so that the floor or part will be free to sag or fall in a fire without causing structural damage to the shaft; and
any internal wall which is required to have an FRL with respect to integrity and insulation, except a wall that bounds a sole-occupancy unit in the topmost (or only) storey and there is only one unit in that storey, must extend to—
the underside of the floor next above if that floor has an FRL of at least 30/30/30; or
the underside of a ceiling having a resistance to the incipient spread of fire to the space above itself of not less than 60 minutes; or
the underside of the roof covering if it is non-combustible and, except for roof battens with dimensions of 75 mm x 50 mm or less or sarking-type material, must not be crossed by timber or other combustible building elements; or
450 mm above the roof covering if it is combustible; and
a load bearing internal wall and a load bearing fire wall (including those that are part of a load bearing shaft) must be constructed from—
concrete; or
masonry; or
subject to (2), fire-protected timber; or
any combination of (i) to (iii); and
in a Class 5, 6, 7, 8 or 9 building, in the storey immediately below the roof, internal columns and internal walls other than fire walls and shaft walls, need not comply with Tables S5C21e, S5C21f and S5C21g; and
in a Class 2 or 3 building, except where within the one sole-occupancy units, or a Class 9a health-care building or a Class 9b building, a floor separating storeys or above a space for the accommodation of motor vehicles or used for storage or any other ancillary purpose, must—
be constructed so that it is at least of the standard achieved by a floor/ceiling system incorporating a ceiling which has a resistance to the incipient spread of fire to the space above itself of not less than 60 minutes; or
have an FRL of at least 30/30/30; or
have a fire-protective covering on the underside of the floor, including beams incorporated in it, if the floor is combustible or of metal; and
in a Class 9c building a floor above a space for the accommodation of motor vehicles or used for storage or any other ancillary purpose, and any column supporting the floor must—
be constructed so that it is at least of the standard achieved by a floor/ceiling system incorporating a ceiling which has a resistance to the incipient spread of fire to the space above itself of not less than 60 minutes; or
have an FRL of at least 30/30/30; or
have a fire-protective covering on the underside of the floor, including beams incorporated in it, if the floor is combustible or of metal.
(2) For the purposes of (1)(d)(iii), fire-protected timber may be used, provided that—
the building is—
a separate building; or
a part of a building—
which only occupies part of a storey, and is separated from the remaining part by a fire wall; or
which is located above or below a part not containing fire-protected timber and the floor between the adjoining parts is provided with an FRL not less than that prescribed for a fire wall for the lower storey; and
the building has an effective height of not more than 25 m; and
the building has a sprinkler system (other than a FPAA101D or FPAA101H system) throughout complying with Specification 17; and
any insulation installed in the cavity of the timber building element required to have an FRL is non-combustible; and
cavity barriers are provided in accordance with Specification 9.
(3) For the purposes of Table S5C21a and Table S5C21b, external wall includes any column and other building element incorporated within it or other external building element.
Table S5C21a Type B construction: FRL of loadbearing parts of external walls
Distance from a fire-source feature
FRL (in minutes) Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part
Class 5, 7a or 9
Class 6
Class 7b or 8
Less than 1.5 m
90/90/90
120/120/120
180/180/180
240/240/240
1.5 to less than 3 m
90/60/30
120/90/60
180/120/90
240/180/120
3 m to less than 9 m
90/30/30
120/30/30
180/90/60
240/90/60
9 m to less than 18 m
90/30/–
120/30/–
180/60/–
240/60/–
18 m or more
–/–/–
–/–/–
–/–/–
–/–/–
Table S5C21b Type B construction: FRL of non-loadbearing parts of external walls
Distance from a fire-source feature
FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part
Class 5, 7a or 9
Class 6
Class 7b or 8
Less than 1.5 m
–/90/90
–/120/120
–/180/180
–/240/240
1.5 m to less than 3 m
–/60/30
–/90/60
–/120/90
–/180/120
3 m or more
–/–/–
–/–/–
–/–/–
–/–/–
Table S5C21c Type B construction: FRL of external columns not incorporated in an external wall
Distance from a fire-source feature
FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part
Class 5, 7a or 9
Class 6
Class 7b or 8
Load bearing column — less than 18 m
90/–/–
120/–/–
180/–/–
240/–/–
Load bearing column — 18 m or more
–/–/–
–/–/–
–/–/–
–/–/–
Non-load bearing column
–/–/–
–/–/–
–/–/–
–/–/–
Table S5C21d Type B construction: FRL of common walls and fire walls
Wall type
FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part
Class 5, 7a or 9
Class 6
Class 7b or 8
Load bearing or non-load bearing
90/90/90
120/120/120
180/180/180
240/240/240
Table S5C21e Type B construction: FRL of loadbearing internal walls
Location
FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part
Class 5, 7a or 9
Class 6
Class 7b or 8
Fire-resisting lift and stair shafts
90/90/90
120/120/120
180/120/120
240/120/120
Bounding public corridors, public lobbies and the like
60/60/60
120/–/–
180/–/–
240/–/–
Between or bounding sole-occupancy units
60/60/60
120/–/–
180/–/–
240/–/–
Table S5C21f Type B construction: FRL of non-loadbearing internal walls
Location
FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part
Class 5, 7a or 9
Class 6
Class 7b or 8
Fire-resisting stair shafts
–/90/90
–/120/120
–/120/120
–/120/120
Bounding public corridor, public lobbies and the like
–/60/60
–/–/–
–/–/–
–/–/–
Between or bounding sole-occupancy units
–/60/60
–/–/–
–/–/–
–/–/–
Table S5C21g Type B construction: FRL of other building elements not covered by Tables S5C21a to S5C21f
Building element
FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part
Class 5, 7a or 9
Class 6
Class 7b or 8
Other load bearing internal walls and columns
60/–/–
120/–/–
180/–/–
240/–/–
Roofs
–/–/–
–/–/–
–/–/–
–/–/–
Tables
- Table S5C21a Type B construction: FRL of loadbearing parts of external walls
- Table S5C21b Type B construction: FRL of non-loadbearing parts of external walls
- Table S5C21c Type B construction: FRL of external columns not incorporated in an external wall
- Table S5C21d Type B construction: FRL of common walls and fire walls
- Table S5C21e Type B construction: FRL of loadbearing internal walls
- Table S5C21f Type B construction: FRL of non-loadbearing internal walls
- Table S5C21g Type B construction: FRL of other building elements not covered by Tables S5C21a to S5C21f
Changed since NCC 2022. See NCC 2022 Volume One S5C21, or show what changed.
(1) In a building required to be of Type B … above the roof covering if it is combustible; and a loadbearing load bearing internal wall and a loadbearing load bearing fire wall (including those that are part of a loadbearing load bearing shaft) must be constructed from — concrete; or masonry; or … 5, 7a or 9 Class 6 Class 7b or 8 Loadbearing Load bearing column — less than 18 m 90/–/– 120/–/– 180/–/– 240/–/– Loadbearing Load bearing column — 18 m or more –/–/– –/–/– –/–/– –/–/– Non-loadbearing Non-load bearing column –/–/– –/–/– –/–/– –/–/– Table S5C21d Type B construction: … 5, 7a or 9 Class 6 Class 7b or 8 Loadbearing Load bearing or non-loadbearing non-load bearing 90/90/90 120/120/120 180/180/180 240/240/240 Table S5C21e Type B construction: FRL … 7a or 9 Class 6 Class 7b or 8 Fire-resisting lift and stair shafts –/90/90 –/120/120 –/120/120 –/120/120 Bounding public corridor, public … 7a or 9 Class 6 Class 7b or 8 Other loadbearing load bearing internal walls and columns 60/–/– 120/–/– 180/–/– 240/–/– Roofs –/–/– –/–/– –/–/– –/–/–
Removed words are struck through; added words are highlighted. Comparison of the text only.