VIC D3D26 Operation of latch
VIC Part D3 Construction of exits · varies D3D26 Operation of latch
Delete subclause D3D26(1) and insert VIC D3D26(1) as follows:
(1) A door in a required exit, forming part of a required exit or in the path of travel to a required exit must be readily openable without a key from the side that faces a person seeking egress, by—
a single hand downward action on a single device which—
for a door in a required exit in an early early childhood centre that does not open to an outdoor space enclosed in accordance with G1D4 —
is located between 1.5 m and 1.65 m above the floor; and
returns the door to the fully closed position immediately after each opening; and
in all other locations, located between 900 mm and 1.1 m above the floor; and
if serving an area required to be accessible by Part D4—
be such that the hand of a person who cannot grip will not slip from the handle during the operation of the latch; and
have a clearance between the handle and the back plate or door face at the centre grip section of the handle of not less than 35 mm and not more than 45 mm; or
a single hand pushing action on a single device which—
for a door in a required exit in an early childhood centre that does not open to an outdoor space enclosed in accordance with G1D4 —
is located between 1.5 m and 1.65 m above the floor; and
returns the door to the full closed position immediately after each opening; and
in all other locations, is located between 900 mm and 1.2 m above the floor.
Changed since NCC 2022. See NCC 2022 Volume One VIC D3D26, or show what changed.
Insert Delete subclause D3D26(1) and insert VIC subclause D3D26(6) in clause D3D26 D3D26(1) as follows: (6) For (1) A door in a required exit, forming part of a required exit or in the purposes path of (1), travel to a required exit must be readily openable without a key from the side that faces a person seeking egress, by — a single hand downward action on a single device which — for a door in a required exit in an exit door from a children’s service which early early childhood centre that does not open to an outdoor space enclosed in accordance with G1D4, must have the device G1D4 — is located between 1.5 m and 1.65 m above the floor floor; and returns the door to the fully closed position immediately after each opening; and in all other locations, located between 900 mm and 1.1 m above the floor; and if serving an area required to be accessible by Part D4 — be such that the hand of a person who cannot grip will not slip from the handle during the operation of the latch; and have a clearance between the handle and the back plate or door must be self-closing. face at the centre grip section of the handle of not less than 35 mm and not more than 45 mm; or a single hand pushing action on a single device which — for a door in a required exit in an early childhood centre that does not open to an outdoor space enclosed in accordance with G1D4 — is located between 1.5 m and 1.65 m above the floor; and returns the door to the full closed position immediately after each opening; and in all other locations, is located between 900 mm and 1.2 m above the floor.