13.2.4 Roof lights
Part 13.2 Building fabric · NCC 2019: 3.12.1.3
Roof lights (including any associated shaft and diffuser) serving a habitable room or an interconnecting space such as a corridor, hallway, stairway or the like must have—
a total area of not more than 5% of the floor area of the room or space served; and
transparent and translucent elements, including any imperforate ceiling diffuser, with a combined performance of—
for Total System SHGC, in accordance with Table 13.2.4; and
for Total System U-Value, not more than U3.9.
Table 13.2.4 Roof lights – Total System SHGC
Roof light shaft index Note 1
Total area of roof lights up to 3.5% of the floor area of the room or space
Total area of roof lights more than 3.5% and up to 5% of the floor area of the room or space
< 1.0
≤ 0.45
≤ 0.29
≥ 1.0 to < 2.5
≤ 0.51
≤ 0.33
≥ 2.5
≤ 0.76
≤ 0.49
Table Notes
The roof light shaft index is determined by measuring the distance from the centre of the shaft at the roof to the centre of the shaft at the ceiling level and dividing it by the average internal dimension of the shaft opening at the ceiling level (or the diameter for a circular shaft) in the same units of measurement.
The area of a roof light is the area of the roof opening that allows light to enter the building. The total area of roof lights is the combined area for all roof lights serving the room or space.
Tables
State and territory variations all clauses side by side →
- NSW Doesn't apply This clause been deliberately left blank 13.2.4 does not apply in NSW.
- NT Varied Roof lights serving a habitable room or an interconnecting space such as a corridor, hallway, stairway or the like— if the total…