Table 13.2.4 Roof lights – Total System SHGC
| Roof light shaft index Note 1 | Total area of roof lights up to 3.5% of the floor area of the room or space | Total area of roof lights more than 3.5% and up to 5% of the floor area of the room or space |
|---|---|---|
| < 1.0 | ≤ 0.45 | ≤ 0.29 |
| ≥ 1.0 to < 2.5 | ≤ 0.51 | ≤ 0.33 |
| ≥ 2.5 | ≤ 0.76 | ≤ 0.49 |
Table Notes
The roof light shaft index is determined by measuring the distance from the centre of the shaft at the roof to the centre of the shaft at the ceiling level and dividing it by the average internal dimension of the shaft opening at the ceiling level (or the diameter for a circular shaft) in the same units of measurement.
The area of a roof light is the area of the roof opening that allows light to enter the building. The total area of roof lights is the combined area for all roof lights serving the room or space.
Table for 13.2.4 Roof lights
Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 Table 13.2.4.