Deemed-to-Satisfy Provision · NCC 2022 Volume One

C3D8 Separation by fire walls

Part C3 Compartmentation and separation · NCC 2019: C2.7

Open C3D8 on NCC Online ↗

(1) Construction — A fire wall must be constructed in accordance with the following:

The fire wall has the relevant FRL prescribed by Specification 5 for each of the adjoining parts, and if these are different, the greater FRL, except where S5C19(3)(c)(i), S5C22(3)(c)(i) and S5C25(3)(c)(i) permit a lower FRL on the carpark side.

Any openings in a fire wall must not reduce the FRL required by Specification 5 for the fire wall, except where permitted by the Deemed-to-Satisfy Provisions of Part C4.

Building elements, other than roof battens with dimensions of 75 mm x 50 mm or less or sarking-type material, must not pass through or cross the fire wall unless the required fire-resisting performance of the fire wall is maintained.

(2) Separation of buildings — A part of a building separated from the remainder of the building by a fire wall may be treated as a separate building for the purposes of the Deemed-to-Satisfy Provisions of Sections C, D and E if it is constructed in accordance with (1) and the following:

The fire wall extends through all storeys and spaces in the nature of storeys that are common to that part and any adjoining part of the building.

The fire wall is carried through to the underside of the roof covering.

Where the roof of one of the adjoining parts is lower than the roof of the other part, the fire wall extends to the underside of—

the covering of the higher roof, or not less than 6 m above the covering of the lower roof; or

the lower roof if it has an FRL not less than that of the fire wall and no openings closer than 3 m to any wall above the lower roof; or

the lower roof if its covering is non-combustible and the lower part has a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17.

(3) Separation of fire compartments — A part of a building separated from the remainder of the building by a fire wall may be treated as a separate fire compartment if it is constructed in accordance with (a) and the fire wall extends to the underside of—

a floor having an FRL required for a fire wall; or

the roof covering.

Changed in NCC 2025 (minor wording). See NCC 2025 Volume One C3D8, or show what changed.

(1) Construction — A fire wall must be constructed in … separate fire compartment if it is constructed in accordance with (a) (1) and the fire wall extends to the underside of — a floor having an FRL required for a fire wall; or the roof covering.

Removed words are struck through; added words are highlighted. Comparison of the text only.

Can't meet C3D8? A Performance Solution must meet the Performance Requirements it satisfies: C1P1, C1P2, C1P3, C1P4, C1P5, C1P6, C1P7, C1P8, C1P9. Start a Performance Solution →