D2D21 Plant rooms, lift machine rooms and electricity network substations: Concession
Part D2 Provision for escape · NCC 2019: D1.16
(1) A ladder may be used in lieu of a stairway to provide egress from—
a plant room with a floor area of not more than 100 m2; or
all but one point of egress from a plant room, a lift machine room or a Class 8 electricity network substation with a floor area of not more than 200 m2.
(2) A ladder permitted under (1)—
may—
form part of an exit provided that in the case of a fire-isolated stairway it is contained within the shaft; or
discharge within a storey in which case it must be considered as forming part of the path of travel; and
for a plant room or a Class 8 electricity network substation, must comply with AS 1657; and
for a lift machine room, where access is provided from within a machine room to a secondary floor, a fixed rung type ladder complying with AS 1657 may be used, provided that—
the height between the floors is not more than 2800 mm; and
the ladder is inclined at an angle to the horizontal not less than 65 degrees nor more than 75 degrees; and
the distance between the front face of the ladder and any adjacent obstruction is not less than—
960 mm, where the ladder is inclined 65 degrees to the horizontal; or
760 mm, where the ladder is inclined 75 degrees to the horizontal; or
a distance that is determined by interpolating the values in (A) and (B), where the ladder is inclined at any angle between 65 degrees and 75 degrees to the horizontal; and
a clear space not less than 600 mm exists between the foot of the ladder and any equipment.