Deemed-to-Satisfy Provision · NCC 2022 Volume One

D2D23 Egress from primary schools

Part D2 Provision for escape · NCC 2019: D1.18

Open D2D23 on NCC Online ↗

(1) Every part of a Class 9b primary school must be wholly within a storey that provides direct egress to a road or open space.

(2) The requirements of (1) do not apply to a building with a rise in storeys of 4 or less, where the primary school is the only use in that building.

Applications

For D2D23(1), a primary school includes classrooms, offices, staffrooms, halls, canteens and the like within the primary school.

For D2D23(2), a primary school includes classrooms, offices, staffrooms, halls, canteens, carparks, end of trip facilities and the like provided solely for the primary school, or school which incorporates the primary school.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One D2D23.
Can't meet D2D23? A Performance Solution must meet the Performance Requirements it satisfies: D1P1, D1P2, D1P3, D1P4, D1P5, D1P6, D1P8, D1P9. Start a Performance Solution →