D3D27 Re-entry from fire-isolated exits
Part D3 Construction of exits · NCC 2019: D2.22
(1) Doors of a fire-isolated exit must not be locked from the inside as follows:
In a Class 9a health-care building.
In a Class 9b early childhood centre.
In a Class 9c building.
In a fire-isolated exit serving any storey above an effective height of 25 m, throughout the exit.
(2) The requirements of (1)(a), (c) and (d) do not apply to a door fitted with a fail-safe device that automatically unlocks the door upon the activation of a fire alarm and—
on at least every fourth storey, the doors are not able to be locked and a sign is fixed on such doors stating that re-entry is available; or
an intercommunication system, or an audible or visual alarm system, operated from within the enclosure is provided near the doors and a sign is fixed adjacent to such doors explaining its purpose and method of operation.
(3) The requirements of (1)(b) do not apply to a door fitted with a fail-safe device that automatically unlocks the door serving the Class 9b early childhood centre upon the activation of a fire alarm.
Changed in NCC 2025. See NCC 2025 Volume One D3D27, or show what changed.
(1) Doors of a fire-isolated exit must not be locked from the inside as follows: In a Class 9a health-care 2 building. In a Class 9b early childhood centre. 3 building. In a Class 9c 6 building. In a Class 7a building. In a Class 9 building. In a fire-isolated exit serving any storey above an effective height of 25 m, throughout the exit. (2) The requirements of (1)(a), (c) and (d) (1) do not apply to a door, other than a door in a Class 9b early childhood centre, fitted with a fail-safe device that automatically unlocks the door upon the activation of a fire alarm and — re-entry is facilitated by — on at least every fourth storey, the doors are … is fixed on such doors stating that re-entry is available; and on at least every second storey where re-entry is not available, a sign is fixed to the wall within the fire-isolated exit within 1.5 m of the exit door stating the location of nearby re-entry; or an intercommunication system, or an audible or visual alarm system, operated from within the enclosure is provided near the doors on at least every fourth storey, and a sign is fixed adjacent to such doors explaining its purpose and method of operation. operation, and on at least every second storey where re-entry is not available, a sign is fixed to the wall within the fire-isolated exit within 1.5 m of the exit door stating the location of a nearby intercommunication system. (3) The requirements of (1)(b) (1)(e) do not apply to a door in a Class 9b early childhood centre fitted with a fail-safe device that automatically unlocks the door serving the Class 9b early childhood centre upon the activation of a fire alarm.