Deemed-to-Satisfy Provision · NCC 2022 Volume One

D3D9 Enclosure of space under stairs and ramps

Part D3 Construction of exits · NCC 2019: D2.8

Open D3D9 on NCC Online ↗

(1) Fire-isolated stairways and ramps — If the space below a required fire-isolated stairway or fire-isolated ramp is within the fire-isolated shaft, it must not be enclosed to form a cupboard or similar enclosed space.

(2) Non fire-isolated stairways and ramps — The space below a required non fire-isolated stairway (including an external stairway) or non fire-isolated ramp must not be enclosed to form a cupboard or other enclosed space unless—

the enclosing walls and ceilings have an FRL of not less than 60/60/60; and

any access doorway to the enclosed space is fitted with a self-closing –/60/30 fire door.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One D3D9.
Can't meet D3D9? A Performance Solution must meet the Performance Requirements it satisfies: D1P1, D1P2, D1P3, D1P4, D1P5, D1P6, D1P8, D1P9. Start a Performance Solution →