Deemed-to-Satisfy Provision · NCC 2022 Volume One

D3D11 Pedestrian ramps

Part D3 Construction of exits · NCC 2019: D2.10

Open D3D11 on NCC Online ↗

(1) A fire-isolated ramp may be substituted for a fire-isolated stairway if the construction enclosing the ramp and the width and ceiling height comply with the requirements for a fire-isolated stairway.

(2) A ramp serving as a required exit must—

where the ramp is also serving as an accessible ramp under Part D4, be in accordance with AS 1428.1; or

in any other case, have a gradient not steeper than 1:8.

(3) The floor surface of a ramp must have a slip-resistance classification not less than that listed in Table D3D15 when tested in accordance with AS 4586.

Changed in NCC 2025. See NCC 2025 Volume One D3D11, or show what changed.

(1) A fire-isolated ramp may be substituted for a fire-isolated … not steeper than 1:8. (3) The floor surface of a ramp ramp, other than a threshold ramp, must have a slip-resistance classification not less than that listed in Table D3D15 when tested in accordance with AS 4586.

Removed words are struck through; added words are highlighted. Comparison of the text only.

Can't meet D3D11? A Performance Solution must meet the Performance Requirements it satisfies: D1P1, D1P2, D1P3, D1P4, D1P5, D1P6, D1P8, D1P9. Start a Performance Solution →