Deemed-to-Satisfy Provision · NCC 2022 Volume One

E2D13 Basements (other than Class 7a buildings)

Part E2 Smoke hazard management · NCC 2019: Table E2.2a

Open E2D13 on NCC Online ↗

(1) A basement, other than a Class 7a basement, not counted in the rise in storeys in accordance with C2D3, must—

comply with measures in accordance with this Part applicable to the building generally; and

where the basement has a total floor area of more than 2000 m2, be provided with—

if not more than 2 below ground storeys—

a zone pressurisation system between vertically separated fire compartments in accordance with AS 1668.1, if the basement has more than one fire compartment; or

an automatic smoke detection and alarm system complying with Specification 20; or

a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17; or

if more than 2 below ground storeys, a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17.

(2) For the purposes of (1), ‘vertically separated fire compartments’ are fire compartments above and below each other, and not fire compartments within the same storey.

Notes

Refer to E2D14 to E2D20 for specific provisions applicable to a Class 6 (in a fire compartment having a floor area of more than 2000 m2) and Class 9b building or part of a building.

Basements with more than 3 below ground storeys or containing Class 6 or 9b occupancies with a large number of occupants may require special consideration in accordance with E2D21.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One E2D13.
Can't meet E2D13? A Performance Solution must meet the Performance Requirements it satisfies: E2P1, E2P2. Start a Performance Solution →