Deemed-to-Satisfy Provision · NCC 2022 Volume One

E2D6 Buildings more than 25 m in effective height: Class 5, 6, 7b, 8 and 9b buildings

Part E2 Smoke hazard management · NCC 2019: Table E2.2a

Open E2D6 on NCC Online ↗

(1) A Class 5, 6, 7b, 8 or 9b building or part of a building must be provided with a zone pressurisation system between vertically separated fire compartments in accordance with AS 1668.1, if the building is more than 25 m in effective height.

(2) The requirements of (1) do not apply to a building that has a fire compartment containing a Class 5, 6, 7b, 8 or 9b part (or a combination of these classes in the same fire compartment) where there is only one fire compartment containing these classifications in an otherwise Class 2, 3, 9a or 9c building.

(3) For the purposes of (1), ‘vertically separated fire compartments’ are fire compartments above and below each other, and not fire compartments within the same storey.

Notes

Refer to E2D14 to E2D20 for specific provisions applicable to a Class 6 (in a fire compartment having a floor area of more than 2000 m2) and Class 9b building or part of a building.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One E2D6.
Can't meet E2D6? A Performance Solution must meet the Performance Requirements it satisfies: E2P1, E2P2. Start a Performance Solution →