Deemed-to-Satisfy Provision · NCC 2022 Volume One

F7D4 Determination of impact sound insulation ratings

Part F7 Sound transmission and insulation · NCC 2019: NT F5.3, F5.3

Open F7D4 on NCC Online ↗
Varied in NT. Check the variation for your state.

(1) A floor in a building required to have an impact sound insulation rating must—

have the required value for weighted normalised impact sound pressure level (Ln,w) determined in accordance with AS ISO 717.2 using results from laboratory measurements; or

comply with Specification 28.

(2) A wall in a building required to have an impact sound insulation rating must—

for a Class 2 or 3 building be of discontinuous construction and

for a Class 9c building, must—

for other than masonry, be two or more separate leaves without rigid mechanical connection except at the periphery; or

be identical with a prototype that is no less resistant to the transmission of impact sound when tested in accordance with Specification 29 than a wall listed in S28C4 to S28C7.

(3) For the purposes of this Part, discontinuous construction means a wall having a minimum 20 mm cavity between 2 separate leaves, and—

for masonry, where wall ties are required to connect leaves, the ties are of the resilient type; and

for other than masonry, there is no mechanical linkage between leaves except at the periphery.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One F7D4.
Can't meet F7D4? A Performance Solution must meet the Performance Requirements it satisfies: F7P1, F7P2, F7P3, F7P4. Start a Performance Solution →

State and territory variations all clauses side by side →

Clauses referred to

Defined terms used