Deemed-to-Satisfy Provision · NCC 2022 Volume One

J3D14 Net equivalent energy usage of a sole-occupancy unit of a Class 2 building or a Class 4 part of a building

Part J3 Elemental provisions for a sole-occupancy unit of a Class 2 building or a Class 4 part of a building

Open J3D14 on NCC Online ↗
Varied in NSW. Check the variation for your state.

(1) The net equivalent energy usage of a sole-occupancy unit of a Class 2 building or Class 4 part of a building, calculated in accordance with (a), must not exceed the allowance calculated in accordance with (b)—

[formula] , where—

[formula] = the floor area factor obtained from multiplying the total floor area by the adjustment factor in Table J3D14a; and

[formula] = the main space conditioning and main water heater efficiency factor obtained from the ABCB Standard for Whole-of-Home Efficiency Factors; and

[formula] = the swimming pool pump energy usage in (2); and

[formula] = the spa pump energy usage in (3); and

[formula] = the installed capacity of on-site photovoltaics apportioned to the sole-occupancy unit of a Class 2 building or Class 4 part of a building (kW); and

[formula] , where—

[formula] = the floor area factor obtained from multiplying the total floor area by the adjustment factor in Table J3D14a; and

[formula] = the energy factor obtained from Table J3D14b.

(2) The swimming pool pump energy usage (EP) must be determined in accordance with the following formula: [formula] , where—

[formula] = the swimming pool pump energy usage; and

[formula] = the volume of the swimming pool to the nearest 1000 litres; and

[formula] = the swimming pool pump factor in Table 13.6.2c of the ABCB Housing Provisions.

(3) The spa pump energy usage (ES) must be determined in accordance with the following formula: [formula] ,where—

[formula] = the spa pump energy usage; and

[formula] = the volume of the spa to the nearest 100 litres; and

[formula] = the spa pump factor in Table 13.6.2d of the ABCB Housing Provisions.

Table J3D14a Floor area adjustment factor for a sole-occupancy unit of a Class 2 building or a Class 4 part of a building

Total floor area m2

Floor area factor

Total floor area m2

Floor area factor

Total floor area m2

Floor area factor

Total floor area m2

Floor area factor

< 50

0.0123

160–169

0.0097

280–289

0.0087

400–409

0.0080

50–59

0.0119

170–179

0.0096

290–299

0.0086

410–419

0.0079

60–69

0.0116

180–189

0.0095

300–309

0.0085

420–429

0.0079

70–79

0.0113

190–199

0.0094

310–319

0.0085

430–439

0.0078

80–89

0.0111

200–209

0.0093

320–329

0.0084

440–449

0.0078

90–99

0.0108

210–219

0.0092

330–339

0.0083

450–459

0.0077

100–109

0.0106

220–229

0.0091

340–349

0.0083

460–469

0.0077

110–119

0.0105

230–239

0.0090

350–359

0.0082

470–479

0.0077

120–129

0.0103

240–249

0.0090

360–369

0.0082

480–489

0.0076

130–139

0.0101

250–259

0.0089

370–379

0.0081

490–499

0.0076

140–149

0.0100

260–269

0.0088

380–389

0.0081

500

0.0075

150–159

0.0099

270–279

0.0087

390–399

0.0080

—

—

Table Notes

The total floor area is measured within the inside face of the external walls of the sole-occupancy unit and includes any conditioned attached Class 10a building.

Where values fall between ranges given, the floor area must be rounded up to the nearest whole square metres of floor area.

Table J3D14b Energy factor for a sole-occupancy unit of a Class 2 building or a Class 4 part of a building

Climate zone

ACT

NSW

NT

QLD

SA

TAS

Vic

WA

1

—

—

2.73

3.95

—

—

—

4.64

2

—

1.88

—

2.54

—

—

—

—

3

—

—

1.76

3.52

—

—

—

4.10

4

—

2.57

—

—

2.65

—

1.79

3.34

5

—

2.50

—

3.26

2.56

—

—

3.36

6

—

3.43

—

—

3.58

—

2.32

4.58

7

3.66

3.32

—

—

—

4.41

2.32

—

8

—

5.70

—

—

—

5.60

4.02

—

Tables

Changed in NCC 2025. See NCC 2025 Volume One J3D14, or show what changed.

(1) The net equivalent energy usage of a sole-occupancy unit of a Class 2 building or Class 4 part of a building, calculated in accordance with (a), building must not exceed the allowance calculated determined in accordance with (b)— the following formula: [formula] , where — [formula] = the floor area factor obtained from multiplying the total floor area by the adjustment factor in Table J3D14a; and [formula] = the energy factor obtained from Table J3D14b. (2) For the purposes of (1), the net equivalent energy usage must be calculated — where the Class 4 part of a building is served by a dedicated heated water system, in accordance with (3); and where the Class 4 part of a building is served by a centralised heated water system, in accordance with (4). (3) The net equivalent energy usage of a Class 4 part of a building served by a dedicated heated water system must be determined in accordance with the following formula: [formula] , where — [formula] = the floor area factor … and [formula] = the swimming pool pump energy usage in (2); (5); and [formula] = the spa pump energy usage in (3); (6); and [formula] = the installed capacity of a on-site photovoltaics apportioned to the sole-occupancy unit of a Class 2 building or Class 4 part of a building (kW); and (4) The net equivalent energy usage of a Class 4 part of a building served by a centralised heated water system must be determined in accordance with the following formula: [formula] , where — [formula] = the floor area factor … by the adjustment factor in Table J3D14a; and [formula] = subject to (7), the energy main space conditioning and main water heater efficiency factor obtained from Table J3D14b. (2) the ABCB Standard for Whole-of-Home Efficiency Factors; and [formula] = the swimming pool pump energy usage in (5); and [formula] = the spa pump energy usage in (6); and [formula] = the centralised heated water system circulating pump energy usage in (8); and [formula] = the installed capacity, in kW, of on-site photovoltaics apportioned to the Class 4 part of a building; and [formula] = the installed capacity, in kW, of on-site photovoltaics that directly offsets the energy consumption of circulating pumps for a centralised heated water system serving a Class 4 part of a building, where — this value does not exceed circulating pump energy usage [formula] ; and the on-site solar photovoltaics are directly connected to the same electrical supply as common area equipment in the building, including the circulating pumps. (5) The swimming pool pump energy usage (EP) for a swimming pool dedicated solely to the Class 4 part of a building must be determined in accordance with the following formula: [formula] … pump factor in Table 13.6.2c of the ABCB Housing Provisions. (3) (6) The spa pump energy usage (ES) must be determined in … pump factor in Table 13.6.2d of the ABCB Housing Provisions. (7) The main space conditioning and main water heater efficiency factor for a Class 4 part of a building served by a centralised heated water system must be determined in accordance with the following — for other than a solar boosted centralised heated water system, the equivalent water heater used to the determine the efficiency factor in the ABCB Standard for Whole-of-Home Efficiency Factors must be determined in accordance with Table J3D14e; and for a solar boosted centralised heated water system, the efficiency factors must be determined in accordance with the following formula: [formula] , where — [formula] = the main space conditioning and main water heater efficiency factor; and [formula] = the efficiency factor obtained from the ABCB Standard for Whole-of-Home Efficiency Factors using the equivalent water heater in Table J3D14e; and [formula] = the efficiency factor obtained from the ABCB Standard for Whole-of-Home Efficiency Factors for — where the solar boosted centralised heated water system uses heat pump type heating as the auxiliary heating source, a heat pump (standard) water heater; and where the solar boosted centralised heated water system uses gas type heating as the auxiliary heating source, a gas storage water heater; and for all other types of solar boosted centralised heated water systems, an electric storage (standard) water heater; and [formula] = the solar percentage factor determined in accordance with the following formula: [formula] , where — [formula] = the solar percentage factor; and [formula] = the total area in m2 of all solar thermal collectors connected to the heated water system; and [formula] = the total floor area in m2 of all sole-occupancy units served by the heated water system. [formula] = the non-solar percentage factor determined in accordance with the following formula: [formula] , where — [formula] = the non-solar percentage factor; and [formula] = the solar percentage factor in (iv); and where the main space conditioning and main water heater efficiency factor for the heat pump [formula] is less than that of the solar boosted system [formula] then [formula] must be set to 0 and [formula] to 1; and [formula] cannot be greater than 1.0. (8) The circulating pump energy usage [formula] must be determined in accordance with the following formula: [formula] , where — [formula] = the circulating pump energy usage; and [formula] = heated water load factor obtained from Table J3D14c; and [formula] = the primary circulating pump energy factor obtained from Table J3D14d; and [formula] = the secondary circulating pump energy factor obtained from Table J3D14d; and [formula] = the factor for the number of sole-occupancy units served determined in accordance with the following formula: [formula] = 0.6 + (number of sole-occupancy units served - 100) x 0.00133; and [formula] = cannot be greater than 1.0. Table J3D14a Floor area adjustment factor for a sole-occupancy unit of a Class 2 building or a Class 4 part of a building Total floor area … metres of floor area. Table J3D14b Energy factor for a sole-occupancy unit of a Class 2 building or a Class 4 part of a building Climate zone ACT NSW … — 8 — 5.70 — — — 5.60 4.02 — Table J3D14c Heated water load factor for a Class 4 part of a building Total floor area m2 Load factor Total floor area m2 Load factor Total floor area m2 Load factor Total floor area m2 Load factor < 50 0.20 160 - 169 0.48 280 - 289 0.59 400 - 409

Removed words are struck through; added words are highlighted. Comparison of the text only.

Can't meet J3D14? A Performance Solution must meet the Performance Requirements it satisfies: J1P1, J1P2, J1P3, J1P4. Start a Performance Solution →

State and territory variations all clauses side by side →

Defined terms used