Table · NCC 2022 Volume One
Table J3D14a Floor area adjustment factor for a sole-occupancy unit of a Class 2 building or a Class 4 part of a building
| Total floor area m2 | Floor area factor | Total floor area m2 | Floor area factor | Total floor area m2 | Floor area factor | Total floor area m2 | Floor area factor |
|---|---|---|---|---|---|---|---|
| < 50 | 0.0123 | 160–169 | 0.0097 | 280–289 | 0.0087 | 400–409 | 0.0080 |
| 50–59 | 0.0119 | 170–179 | 0.0096 | 290–299 | 0.0086 | 410–419 | 0.0079 |
| 60–69 | 0.0116 | 180–189 | 0.0095 | 300–309 | 0.0085 | 420–429 | 0.0079 |
| 70–79 | 0.0113 | 190–199 | 0.0094 | 310–319 | 0.0085 | 430–439 | 0.0078 |
| 80–89 | 0.0111 | 200–209 | 0.0093 | 320–329 | 0.0084 | 440–449 | 0.0078 |
| 90–99 | 0.0108 | 210–219 | 0.0092 | 330–339 | 0.0083 | 450–459 | 0.0077 |
| 100–109 | 0.0106 | 220–229 | 0.0091 | 340–349 | 0.0083 | 460–469 | 0.0077 |
| 110–119 | 0.0105 | 230–239 | 0.0090 | 350–359 | 0.0082 | 470–479 | 0.0077 |
| 120–129 | 0.0103 | 240–249 | 0.0090 | 360–369 | 0.0082 | 480–489 | 0.0076 |
| 130–139 | 0.0101 | 250–259 | 0.0089 | 370–379 | 0.0081 | 490–499 | 0.0076 |
| 140–149 | 0.0100 | 260–269 | 0.0088 | 380–389 | 0.0081 | 500 | 0.0075 |
| 150–159 | 0.0099 | 270–279 | 0.0087 | 390–399 | 0.0080 | — | — |
Table Notes
The total floor area is measured within the inside face of the external walls of the sole-occupancy unit and includes any conditioned attached Class 10a building.
Where values fall between ranges given, the floor area must be rounded up to the nearest whole square metres of floor area.
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table J3D14a.