J5D4 Roof lights
Part J5 Building sealing · NCC 2019: J3.3
(1) A roof light must be sealed, or capable of being sealed, when serving—
a conditioned space; or
a habitable room in climate zones 4, 5, 6, 7 or 8.
(2) A roof light required by (1) to be sealed, or capable of being sealed, must be constructed with—
an imperforate ceiling diffuser or the like installed at the ceiling or internal lining level; or
a weatherproof seal; or
a shutter system readily operated either manually, mechanically or electronically by the occupant.
Changed in NCC 2025. See NCC 2025 Volume One J5D4, or show what changed.
(1) A roof light must be sealed, or capable of being sealed, when serving — a conditioned space; or a habitable room in climate zones 4, 5, 6, 7 or 8. (2) A roof light required by (1) to be sealed, or capable of being sealed, must be constructed with — an imperforate ceiling diffuser or the like installed … readily operated either manually, mechanically or electronically by the occupant.