Deemed-to-Satisfy Provision · NCC 2022 Volume One

J5D5 Windows and doors

Part J5 Building sealing · NCC 2019: J3.4

Open J5D5 on NCC Online ↗
Varied in NSW. Check the variation for your state.

(1) A door, openable window or the like must be sealed—

when forming part of the envelope; or

in climate zones 4, 5, 6, 7 or 8.

(2) The requirements of (1) do not apply to—

a window complying with AS 2047; or

a fire door or smoke door; or

a roller shutter door, roller shutter grille or other security door or device installed only for out-of-hours security.

(3) A seal to restrict air infiltration—

for the bottom edge of a door, must be a draft protection device; and

for the other edges of a door or the edges of an openable window or other such opening, may be a foam or rubber compression strip, fibrous seal or the like.

(4) An entrance to a building, if leading to a conditioned space must have an airlock, self-closing door, rapid roller door, revolving door or the like, other than—

where the conditioned space has a floor area of not more than 50 m2; or

where a café, restaurant, open front shop or the like has—

a 3 m deep un-conditioned zone between the main entrance, including an open front, and the conditioned space; and

at all other entrances to the café, restaurant, open front shop or the like, self-closing doors.

(5) A loading dock entrance, if leading to a conditioned space, must be fitted with a rapid roller door or the like.

Changed in NCC 2025. See NCC 2025 Volume One J5D5, or show what changed.

(1) A door, openable window or the like must be sealed — when forming part of the envelope; or in climate zones 4, 5, 6, 7 or 8. sealed. (2) The requirements of (1) do not apply to — … seal or the like. (4) An entrance to a building, if leading to a conditioned space must have an airlock, self-closing door, rapid roller door, revolving door or the like, other than — where the conditioned space room containing the entrance has a floor area of not more than 50 m2; or where a café, restaurant, open front shop or the like has — a an un-conditioned zone at least 3 m deep un-conditioned zone between the main entrance, including an open front, and the a conditioned space; and at all other entrances to the café, restaurant, open front shop or the like, self-closing doors. doors; or where the entrance is a moveable external wall with the capability to open for the purpose of creating a temporary unconditioned space; or where, for the safety of the building occupants or for the intended use of the facility, it is required to be left open to a temporary unconditioned space at an early childhood centre, preschool, school, or the like; or where the entrance serves a Class 3 sole-occupancy unit or a Class 4 part of a building. (5) A loading dock entrance, if leading to a conditioned space, must be fitted with a rapid roller door or the like.

Removed words are struck through; added words are highlighted. Comparison of the text only.

Can't meet J5D5? A Performance Solution must meet the Performance Requirements it satisfies: J1P1, J1P2, J1P3, J1P4. Start a Performance Solution →

State and territory variations all clauses side by side →

Defined terms used