J5D5 Windows and doors
Part J5 Building sealing · NCC 2019: J3.4
(1) A door, openable window or the like must be sealed—
when forming part of the envelope; or
in climate zones 4, 5, 6, 7 or 8.
(2) The requirements of (1) do not apply to—
a window complying with AS 2047; or
a fire door or smoke door; or
a roller shutter door, roller shutter grille or other security door or device installed only for out-of-hours security.
(3) A seal to restrict air infiltration—
for the bottom edge of a door, must be a draft protection device; and
for the other edges of a door or the edges of an openable window or other such opening, may be a foam or rubber compression strip, fibrous seal or the like.
(4) An entrance to a building, if leading to a conditioned space must have an airlock, self-closing door, rapid roller door, revolving door or the like, other than—
where the conditioned space has a floor area of not more than 50 m2; or
where a café, restaurant, open front shop or the like has—
a 3 m deep un-conditioned zone between the main entrance, including an open front, and the conditioned space; and
at all other entrances to the café, restaurant, open front shop or the like, self-closing doors.
(5) A loading dock entrance, if leading to a conditioned space, must be fitted with a rapid roller door or the like.
Changed in NCC 2025. See NCC 2025 Volume One J5D5, or show what changed.
(1) A door, openable window or the like must be sealed — when forming part of the envelope; or in climate zones 4, 5, 6, 7 or 8. sealed. (2) The requirements of (1) do not apply to — … seal or the like. (4) An entrance to a building, if leading to a conditioned space must have an airlock, self-closing door, rapid roller door, revolving door or the like, other than — where the conditioned space room containing the entrance has a floor area of not more than 50 m2; or where a café, restaurant, open front shop or the like has — a an un-conditioned zone at least 3 m deep un-conditioned zone between the main entrance, including an open front, and the a conditioned space; and at all other entrances to the café, restaurant, open front shop or the like, self-closing doors. doors; or where the entrance is a moveable external wall with the capability to open for the purpose of creating a temporary unconditioned space; or where, for the safety of the building occupants or for the intended use of the facility, it is required to be left open to a temporary unconditioned space at an early childhood centre, preschool, school, or the like; or where the entrance serves a Class 3 sole-occupancy unit or a Class 4 part of a building. (5) A loading dock entrance, if leading to a conditioned space, must be fitted with a rapid roller door or the like.