J6D6 Ductwork insulation
Part J6 Air-conditioning and ventilation · NCC 2019: J5.5
(1) Ductwork and fittings in an air-conditioning system must be provided with insulation—
complying with AS/NZS 4859.1; and
having an insulation R-Value greater than or equal to—
for flexible ductwork, 1.0; or
for cushion boxes, that of the connecting ductwork; or
that specified in Table J6D6.
(2) Insulation must—
be protected against the effects of weather and sunlight; and
be installed so that it—
abuts adjoining insulation to form a continuous barrier; and
maintains its position and thickness, other than at flanges and supports; and
when conveying cooled air—
be protected by a vapour barrier on the outside of the insulation; and
where the vapour barrier is a membrane, be installed so that adjoining sheets of the membrane—
overlap by at least 50 mm; and
are bonded or taped together.
(3) The requirements of (1) do not apply to—
ductwork and fittings located within the only or last room served by the system; or
fittings that form part of the interface with the conditioned space; or
return air ductwork in, or passing through, a conditioned space; or
ductwork for outdoor air and exhaust air associated with an air-conditioning system; or
the floor of an in-situ air-handling unit; or
packaged air conditioners, split systems, and variable refrigerant flow air-conditioning equipment complying with MEPS; or
flexible fan connections.
(4) For the purposes of (1), (2) and (3), fittings—
include non-active components of a ductwork system such as cushion boxes; and
exclude active components such as air-handling unit components.
Table J6D6 Ductwork and fittings – Minimum insulation R-Value
Location of ductwork and fittings
Climate zone 1, 2, 3, 4, 5, 6 or 7
Climate zone 8
Within a conditioned space
1.2
2.0
Where exposed to direct sunlight
3.0
3.0
All other locations
2.0
3.0
Tables
Changed in NCC 2025. See NCC 2025 Volume One J6D6, or show what changed.
(1) Ductwork and fittings in an air-conditioning system must be … system; or the floor of an in-situ air-handling unit; or packaged air conditioners, split systems, and variable refrigerant flow air-conditioning equipment complying with MEPS; or flexible fan connections. (4) For the purposes of (1), (2) and (3), ductwork and fittings — include non-active components of a ductwork system such as cushion boxes; and exclude active components such as air-handling unit components. components, fan coil units of air-conditioning or the like. Table J6D6 Ductwork and fittings – Minimum insulation R-Value Location … to direct sunlight 3.0 3.0 All other locations 2.0 3.0