Table · NCC 2022 Volume One

Table J6D8a Maximum pipework pressure drop – Non-distributive constant speed systems

Part J6 Air-conditioning and ventilation

Open Table J6D8a on NCC Online ↗
Nominal pipe diameter (mm)Maximum pressure drop in systems operating 5000 hours/annum or less (Pa/m)Maximum pressure drop in systems operating more than 5000 hours/annum (Pa/m)
Not more than 20400400
25400400
32400400
40400400
50400350
65400350
80400350
100400200
125400200
150 or more400200

Table for J6D8 Pump systems

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table J6D8a.