Deemed-to-Satisfy Provision · NCC 2025 Volume One

J6D6 Ductwork insulation

Part J6 Air-conditioning and ventilation · NCC 2019: J5.5

Open J6D6 on NCC Online ↗

(1) Ductwork and fittings in an air-conditioning system must be provided with insulation—

complying with AS/NZS 4859.1; and

having an insulation R-Value greater than or equal to—

for flexible ductwork, 1.0; or

for cushion boxes, that of the connecting ductwork; or

that specified in Table J6D6.

(2) Insulation must—

be protected against the effects of weather and sunlight; and

be installed so that it—

abuts adjoining insulation to form a continuous barrier; and

maintains its position and thickness, other than at flanges and supports; and

when conveying cooled air—

be protected by a vapour barrier on the outside of the insulation; and

where the vapour barrier is a membrane, be installed so that adjoining sheets of the membrane—

overlap by at least 50 mm; and

are bonded or taped together.

(3) The requirements of (1) do not apply to—

ductwork and fittings located within the only or last room served by the system; or

fittings that form part of the interface with the conditioned space; or

return air ductwork in, or passing through, a conditioned space; or

ductwork for outdoor air and exhaust air associated with an air-conditioning system; or

the floor of an in-situ air-handling unit; or

flexible fan connections.

(4) For the purposes of (1), (2) and (3), ductwork and fittings—

include non-active components of a ductwork system such as cushion boxes; and

exclude active components such as air-handling unit components, fan coil units of air-conditioning or the like.

Table J6D6 Ductwork and fittings – Minimum insulation R-Value

Location of ductwork and fittings

Climate zone 1, 2, 3, 4, 5, 6 or 7

Climate zone 8

Within a conditioned space

1.2

2.0

Where exposed to direct sunlight

3.0

3.0

All other locations

2.0

3.0

Tables

Changed since NCC 2022. See NCC 2022 Volume One J6D6, or show what changed.

(1) Ductwork and fittings in an air-conditioning system must be … system; or the floor of an in-situ air-handling unit; or packaged air conditioners, split systems, and variable refrigerant flow air-conditioning equipment complying with MEPS; or flexible fan connections. (4) For the purposes of (1), (2) and (3), ductwork and fittings — include non-active components of a ductwork system such as cushion boxes; and exclude active components such as air-handling unit components. components, fan coil units of air-conditioning or the like. Table J6D6 Ductwork and fittings – Minimum insulation R-Value Location … to direct sunlight 3.0 3.0 All other locations 2.0 3.0

Removed words are struck through; added words are highlighted. Comparison of the text only.

Can't meet J6D6? A Performance Solution must meet the Performance Requirements it satisfies: J1P1, J1P2, J1P3, J1P4. Start a Performance Solution →

Defined terms used