S6C6 Walls generally
Specification 6 Structural tests for lightweight construction · NCC 2019: Spec C1.8: 3.4
An external and internal wall of lightweight construction that is required to be fire-resisting, other than one covered by S6C3, S6C4 or S6C5, must be subjected to the following tests and must fulfil the following criteria:
The materials tests of S6C10(a) and the criteria of S6C11(a).
A static test by the imposition of a uniformly distributed load of 0.25 kPa (or its equivalent) in accordance with S6C10(b) and the damage and deflection criteria of S6C11(b) and (c) respectively.
A dynamic test by fall of the impact bag through a height of 100 mm in accordance with S6C10(c) and the damage and deflection criteria of S6C11(b) and (d) respectively.
The surface indentation test of S6C10(d) and the surface indentation criterion of S6C11(e).