South Australia variation · NCC 2022 Volume One

SA F6D6 Ventilation of rooms

Part F6 Light and ventilation · varies F6D6 Ventilation of rooms

Open on NCC Online ↗

Delete clause F6D6 and insert SA F6D6 as follows:

A habitable room, office, shop, factory, workroom, sanitary compartment, bathroom, shower room, laundry and any other room occupied by a person for any purpose must have—

natural ventilation complying with F6D7; or

a mechanical ventilation or air-conditioning system complying with AS 1668.2 and AS/NZS 3666.1; or

in a storage shed or bulk grain storage facility, a ventilation system that provides one air change every six hours using openings that have a total area of the lesser of—

35 m2; or

one percent of the total floor area.

Not in NCC 2025. No SA F6D6 in NCC 2025 Volume One.

The national clause

Other states and territories