Deemed-to-Satisfy Provision · NCC 2022 Volume One

J3D13 Shading of a sole-occupancy unit of a Class 2 building or a Class 4 part of a building

Part J3 Elemental provisions for a sole-occupancy unit of a Class 2 building or a Class 4 part of a building

Open J3D13 on NCC Online ↗
Varied in NSW. Check the variation for your state.

Where shading is required to comply with J3D11 or J3D12, it must—

be provided by an external permanent projection, such as a verandah, balcony, fixed canopy, eaves, shading hood or carport, which—

extends horizontally on both sides of the glazing for a distance greater than or equal to the projection distance P in Figure S37C7; or

provide the equivalent shading to (i) with a reveal or the like; or

be provided by an external shading device, such as a shutter, blind, vertical or horizontal building screen with blades, battens or slats, which—

is capable of restricting at least 80% of the summer solar radiation; and

if adjustable, is readily operated either manually, mechanically or electronically by the building occupants.

Changed in NCC 2025 (minor wording). See NCC 2025 Volume One J3D13, or show what changed.

Where shading is required to comply with J3D11 or J3D12, … than or equal to the projection distance P in Figure S37C7; S37C7a; or provide the equivalent shading to (i) with a reveal … operated either manually, mechanically or electronically by the building occupants.

Removed words are struck through; added words are highlighted. Comparison of the text only.

Can't meet J3D13? A Performance Solution must meet the Performance Requirements it satisfies: J1P1, J1P2, J1P3, J1P4. Start a Performance Solution →

State and territory variations all clauses side by side →