Deemed-to-Satisfy Provision · NCC 2022 Volume Three

C1D5 Water efficiency

Part C1 Sanitary plumbing systems

Open C1D5 on NCC Online ↗

A sanitary plumbing system must ensure the efficient use of drinking water by—

limiting water usage from—

a cistern or flushing device for a urinal, to a flush volume of not more than 2.5 litres for each—

single urinal stall; or

600 mm length of a continuous urinal wall; and

a dual flush cistern or flushing valve that is connected to a water closet pan to a flush volume of not more than—

6 and 3 litres; or

4.5 and 3 litres; or

water saving measures equivalent to or greater than those described in (a).

Applications

The flush volumes of C1D5 may be within a tolerance of—

±0.5 litres for the full flush of a 6/3 litre cistern; or

+0.5 litres for the reduced flush of a 6/3 litre cistern; or

±0.2 litres for a 4.5/3 litre cistern.

Exemptions

The requirements of C1D5 do not apply to a vacuum drainage system.

Same wording in NCC 2025 Volume Three. See NCC 2025 Volume Three C1D5.
Can't meet C1D5? A Performance Solution must meet the Performance Requirements it satisfies: C1P1, C1P2, C1P3, C1P4, C1P5, C1P6, C1P7. Start a Performance Solution →