Verification Method · NCC 2022 Volume Three

C1V5 Stack design

Part C1 Sanitary plumbing systems

Open C1V5 on NCC Online ↗

(1) Compliance with C1P5 relating to pipe sizing is verified for the stack system when—

each stack has a pipe size in accordance with (2); and

ventilation is provided in accordance with (3).

(2) Each stack must have a pipe size in accordance with—

Table C1V5a, where a separate relief vent is not provided; or

Table C1V5b, where a separate relief vent is provided.

(3) Ventilation must comply with the following:

Each stack vent must terminate either to—

the atmosphere or interconnect with another vent in accordance with AS/NZS 3500.2; or

an air admittance valve with a minimum airflow rate equal to 8 times the wastewater design flowrate.

Each stack vent must be sized in accordance with—

Clause 8.5.4 of AS/NZS 3500.2 for stack vents; or

Clause 8.5.3 of AS/NZS 3500.2 for relief vents.

Each relief vent must interconnect with the stack vent at each floor.

Applications

Water closets must be connected to a DN 80 or DN 100 discharge pipe.

Water closets must not be connected to DN 80 where a C1V2 System 1 or C1V4 System 3 is used.

Table C1V5a Stack capacity without a relief vent

Stack Nominal Diameter (DN)

Capacity with square or 88° junction, in litres per second (l/s)

Capacity with sweep or 45° junction, in litres per second (l/s)

65

0.5

0.7

80

2.0

2.5

100

4.0

5.2

150

9.5

12.4

Table C1V5b Stack capacity with a relief vent

Stack Nominal Diameter (DN)

Capacity with square or 88° junction, in litres per second (l/s)

Capacity with sweep or 45° junction, in litres per second (l/s)

65

0.7

0.9

80

2.6

3.4

100

5.6

7.3

150

12.4

18.3

Tables

Not in NCC 2025. No C1V5 in NCC 2025 Volume Three.