C1V5 Stack design
Part C1 Sanitary plumbing systems
(1) Compliance with C1P5 relating to pipe sizing is verified for the stack system when—
each stack has a pipe size in accordance with (2); and
ventilation is provided in accordance with (3).
(2) Each stack must have a pipe size in accordance with—
Table C1V5a, where a separate relief vent is not provided; or
Table C1V5b, where a separate relief vent is provided.
(3) Ventilation must comply with the following:
Each stack vent must terminate either to—
the atmosphere or interconnect with another vent in accordance with AS/NZS 3500.2; or
an air admittance valve with a minimum airflow rate equal to 8 times the wastewater design flowrate.
Each stack vent must be sized in accordance with—
Clause 8.5.4 of AS/NZS 3500.2 for stack vents; or
Clause 8.5.3 of AS/NZS 3500.2 for relief vents.
Each relief vent must interconnect with the stack vent at each floor.
Applications
Water closets must be connected to a DN 80 or DN 100 discharge pipe.
Water closets must not be connected to DN 80 where a C1V2 System 1 or C1V4 System 3 is used.
Table C1V5a Stack capacity without a relief vent
Stack Nominal Diameter (DN)
Capacity with square or 88° junction, in litres per second (l/s)
Capacity with sweep or 45° junction, in litres per second (l/s)
65
0.5
0.7
80
2.0
2.5
100
4.0
5.2
150
9.5
12.4
Table C1V5b Stack capacity with a relief vent
Stack Nominal Diameter (DN)
Capacity with square or 88° junction, in litres per second (l/s)
Capacity with sweep or 45° junction, in litres per second (l/s)
65
0.7
0.9
80
2.6
3.4
100
5.6
7.3
150
12.4
18.3