NCC 2022 Volume Three
Part C2 Sanitary drainage systems
20 clauses · Open on NCC Online ↗
- C2O1 ObjectiveThe Objective of this Part is to— safeguard people from illness, injury or loss (including loss of amenity) due to the failure of a sanitary…
- C2F1 Disposal systemSanitary fixtures and sanitary appliances must be provided with an adequate disposal system that does not impact adversely on occupants of the…
- C2F2 Swimming pool wastewater disposalAdequate means for the disposal of swimming pool water and drainage is to be provided for each swimming pool.
- C2P1 DisposalA sanitary drainage system must ensure sewage is transferred from a sanitary plumbing system to an approved disposal system.
- C2P2 Swimming pool drainage NTA swimming pool must have adequate means of draining the pool in a manner that will not— cause illness to people; or affect other property.
- C2P3 AccessA sanitary drainage system must ensure there is access for maintenance and clearing a blockage.
- C2P4 VentilationA sanitary drainage system must ensure there is adequate ventilation to avoid foul air and gases accumulating in the sanitary drainage and sewerage…
- C2P5 ContaminationA sanitary drainage system must ensure protection against internal contamination. (2) A sanitary drainage system must avoid the entry of water, foul…
- C2P6 Uncontrolled dischargeA sanitary drainage system must avoid blockage and uncontrolled discharge.
- C2P7 DamageA sanitary drainage system must avoid damage from root penetration, superimposed loads or ground movement. (2) A sanitary drainage system must avoid…
- C2V1 Velocity and liquid-to-air ratioCompliance with C2P1 is achieved if the sanitary drainage system is designed to operate with— a liquid-to-air ratio of between 1 to 1 and 0.65 to…
- C2V2 Pressure testing VICCompliance with C2P1 is achieved if the sanitary drainage system passes one or more of the pressure tests set out in Section 15 of AS/NZS 3500.2.
- Table C2V3a Frequency factorsFixture usage | NCC building class | Frequency factor (K) Intermittent use e.g. dwelling, guesthouse or office | Class 1, Class 2, Class 3 or Class…
- Table C2V3b Discharge unitsFixture | System 1 - Discharge Units (DU) | System 2 - Discharge Units (DU) | System 3 - Discharge Units (DU) Basin | 0.5 | 0.3 | 0.3 Shower | 0.6 |…
- C2V3 Determination of sanitary drainage wastewater flowratesCompliance with C2P1 for pipe sizing is verified for each sanitary drainage pipework section when the design flow rate is not less than— the…
- C2D1 Deemed-to-Satisfy ProvisionsWhere a Deemed-to-Satisfy Solution is proposed, Performance Requirements C2P1 to C2P7 are satisfied by complying with C2D2 to C2D5. (2) Where a…
- C2D2 Invert levelsThe invert level of a trap or gully weir must be a minimum of 10 mm higher than the soffit of the pipe to which it connects.
- C2D3 Swimming pool drainagePumped discharge from a swimming pool must connect to the sanitary drainage system in accordance with AS/NZS 3500.2.
- C2D4 General requirements NSW SA TAS VICA sanitary drainage system must be in accordance with AS/NZS 3500.2.
- C2D5 Bushfire prone areasA sanitary drainage system in a designated bushfire prone area must be in accordance with AS 3959.