New South Wales variation · NCC 2022 Volume Three

NSW B2D5 Maximum delivery temperature

Part B2 Heated water services · varies B2D5 Maximum delivery temperature

Open on NCC Online ↗

Delete clause B2D5 and insert NSW B2D5 as follows:

The delivery temperature of heated water at the outlet of each sanitary fixture must be—

not more than 45°C in any—

residential part of an aged care building; or

patient care area in a health-care building; or

part of an early childhood centre, or primary or secondary school, that is used by children; or

any facility designated for use by people with a disability; or

not more than 50°C in all other cases.

Applications

B2D5 applies to all heated water installations for personal hygiene purposes.

Same wording in NCC 2025 Volume Three. See NCC 2025 Volume Three NSW B2D5.

The national clause

Other states and territories