South Australia variation · NCC 2022 Volume Three

SA B2D5 Maximum delivery temperature

Part B2 Heated water services · varies B2D5 Maximum delivery temperature

Open on NCC Online ↗

Delete clause B2D5 and insert SA B2D5 as follows:

(1) The delivery temperature of heated water at the outlet of each sanitary fixture must be—

not more than 45 °C in any—

residential part of an aged care building; or

patient care area in a health-care building; or

part of an early childhood centre, or primary or secondary school, that is used by children; or

designated accessible facility in a common area of a Class 2 building, or in any part of a Class 3, Class 5, Class 6, Class 7, Class 8, Class 9a, 9b, 9c or Class 10 building; or

not more than 50 °C in all other cases.

(2) Heated water services in buildings constructed after 19 October 1995 shall have temperature control in accordance with 1(a) and (b).

(3) All new solar water installations (including solar water heater replacements) shall be in accordance with 1(a) and (b).

(4) Where an existing building is altered or extended in such a way that sanitary fixtures used primarily for personal hygiene purposes are installed in a location where, before the alteration or extension, no such fixture existed, the delivery temperature at the fixture shall be in accordance with 1(a) and (b).

(5) Where a water heater is replaced, a temperature control device is required where such a device was in place prior to the installation of the replaced water heater. The device must meet the requirements of 1 (a) and (b).

Applications

B2D5 applies to all heated water installations intended for personal hygiene.

Changed in NCC 2025. See NCC 2025 Volume Three SA B2D5, or show what changed.

Delete clause B2D5 and insert SA B2D5 as follows: (1) … 3, Class 5, Class 6, Class 7, Class 8, Class 9a, 9 a, 9b, 9c or Class 10 building; or not more than 50 °C in all other cases. (2) Heated water services in buildings constructed after 19 October 1995 shall have temperature control in accordance with 1(a) and (b). (3) All new solar water installations (including solar water heater replacements) shall be in accordance with 1(a) and (b). (4) (3) Where an existing building is altered or extended in such … the fixture shall be in accordance with 1(a) and (b). (5) (4) Where a water heater is replaced, a temperature control device … applies to all heated water installations intended for personal hygiene.